HEATING A COOLING

5F,H

Open-Drive Compressors

of its total capacity. Figure 17 shows the sequence and
number of cylinders that unload with each step.

Capacity control unloader systems consist of 4 major

components:

1. A capacity control valve, which increases or

decreases control oil pressure to the hydraulic relay
piston proportionally when the suction pressure from
the crankcase rises or falls.

SUCTION VALVE

Fig. 36 — Capacity Control (5F20, 5F30)

IF PNEUMATIC CONTROL
IS NOT USED. THIS

PORT MUST BE VENTED

FROM

COMPRESSOR

OIL PUMP,

SUCTION VALVE

DISC -

FROM

CRANKCASE

PRESSURE

CONTROL

OIL

PRESSURE

CRANKCASE
PRESSURE

OIL

PUMP

PRESSURE

Fig. 37 — Capacity Control Operation (5F40. 60; 5H40, 60. 66, 80 and 86)