Fig. 7 — storage tank capacity, Fig. 7 — storage tank capacity refrigerant hoses, Liquid indicator – Carrier 19QA User Manual

Page 8: Filter drier

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

CFC-11 or HCFC-123

CFC-113

Ib(Kg)

This graph is based on 70 F The following multipliers may be used to more accurately determine weights at temperatures
other than 70 F

TEMPERATURE F (C)

40 (4.4)

50 (10)

60 (15 5)

70 (21,1)

80 (26.6)

90 (32 2)

100 (37 7)

MULTIPLIER

1 026

1 018

1 009

1 000

991

982

973

Fig. 7 — Storage Tank Capacity

Refrigerant Hoses

— Four, l/2-in. refrigerant hoses

and 8 ball valves with couplers are factory supplied with
the RMS unit. See Table 1. The refrigerant hoses are used
to transfer liquid and vapor through the Refrigerant Man­
agement System. They are designed to withstand high vac­
uum pressure without collapsing.

When used with the refrigerant hoses, the ball valve and

coupler assembly prevent refrigerant loss. Connect the ball
valve and coupler assembly to each end of the 4 refrigerant
hoses. Hand tighten the ball valve and coupler assembly to
the refrigerant hose. The ball valve and coupler assembly
connect to the RMS unit or chiller, depending upon the type
of operation. The coupler should be hand tightened to the

RMS unit or chiller. Excessive tightening will damage the
rubber gaskets.

Liquid Indicator

— The 1/2 in. liquid indicator (in line

sight glass) is factory supplied. Use the liquid indicator dur­
ing either the liquid refrigerant transfer or the vapor con­

densing process to determine the end point of the process.
When liquid is no longer visible in the glass, the process is
almost complete.

Filter Drier

— The filter drier should be used to recycle

refrigerant. Use the factory supplied filter drier when re­
moving moisture and small particles from the refrigerant.
The filter drier is most effective when used with liquid re­
frigerant. The filter drier holds approximately .39 oz
(11 g) of water. See Table 4.

When cleaning large quantities of saturated refrigerant,

use a field supplied, replaceable core filter drier assembly.
The assembly should have four, 100 in.^ cores. It will re­
move approximately 4.2 oz (118 g) of water.

WATER OUT

WATER IN

NOTE: [ ] indicates millimeters

Fig. 8 — Purge Separator Assembly

Table 4 — Water Solubility In Refrigerant

REFRIGERANT

TYPE

TEMPERATURE

SOLUBILITY

OF WATER IN

REFRIGERANT

(ppm)

GRAMS OF

WATER

PER

1000 LB

OZ

60 F

70

32

1.13

(16 C)

[660]

[303]

[10.7]

CFC-11,

70 F

90

41

1.15

CFC-113,

(21 C)

[770]

[349]

[12.3]

80 F

113

51

1 80

[HCFC-123]

(27 C)

[900]

[408]

[14.4]

90 F

140

64

2.26

(32 C)

[1000]

[453]

[16 0]

LEGEND

ppm

— Parts Per Million

NOTE: [ ] indicates HCFC-123 refrigerant

Advertising