Table 2 - Setting Safety Controls (Contd)

SAFETY OR CONTROL DEVICE

RECOMMENDED SETTING

2. Refrigerant Low-Temperature

Cutout (Fig. 1)

1. Install jumper wire or mechanical block in the chilled

water low-temperature cutout and recycle control.

2. Set the refrigerant low-temperature cutout at 33 F while

reading the temperature gage on side of float chamber.

3. Remove jumper wire or block.

3. Oil Heater Thermostat (Fig. 1)

Set the oil heater thermostat to maintain a minimum oil
reservoir temperature of 145 F at shutdown.

4. Condenser High-Pressure

Cutout (Fig. 1)

CUTOUT ADJUSTMENT .-••c '

COVER-

The condenser high-pressure cutout switch is factory set

to shut the machine down when the condenser pressure

reaches approximately fifteen psig. Isolate the switch, and

check switch setting with a metered supply of air.

RESET

„ ...... ........... ,

BUTTON

CUTOUT SCALE

5. Low Oil Pressure Cutout (Fig. 1)

RANGE (CUT-IN) .

DIAL ADJUSTMENT
REMOVE METAL

COVER------

CUTOUT
ADJUSTMENT

Opens switch contacts on drop in oil pressure. Cutout at
9 psi differential. Cut-in at 14 psi differential. While op­
erating pump manually, note and record reservoir pres­

sure on gage. Remove cap and gasket from oil pressure

regulating valve. Loosen locknut. Turn adjusting screw
counterclockwise to lower oil pressure to within 4 psi of
reservoir pressure. Reset differential to adjust cutout. Set
range (cut-in) by turning adjusting dial clockwise, raising
oil pressure.

6. Antirecycle Timer (Fig. 1)

/TIME SETTING

'LOCKNUT

'

N

TIMER

SWITCHES

Time setting is factory set for 20 minutes. Limits the num­
ber of machine starts to three per hour.