Carrier 38ED User Manual

Air-cooled condensing units, Installation, start-up " and service instructions

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Number One
Ar Conditioning
Maker

O

c

c

Installation,

Start-Up

"

and Service Instructions

Carrier Parkway • Syracuse, N Y 13221

Air-Cooled Condensing Units

INDEX

Page

SAFETY CONSIDERATIONS.................................. 1

INSTALLATION........................................................1-6

Step 1 — Check Equipment and

Jobsite................................................................ 1

• UNPACK UNIT
• INSPECT EQUIPMENT

• COMPLETE OR CONSIDER

SYSTEM REQUIREMENTS

Step 2 — Make Piping Connections_________ 2

• REPLACE THE ACCURATER™

REFRIGERANT CONTROL

PISTON IN THE INDOOR
COIL IF REQUIRED

• CONNECT REFRIGERANT LINES

Step 3 — Install Solenoid on Indoor

Coil Liquid Line Fitting......................................3

Step 4 — Make Electrical

Connections....................................................... 4

• INSTALL A BRANCH CIRCUIT

DISCONNECT PER NEC

• ROUTE LINE POWER LEADS INTO

UNIT

• CONNECT GROUND LEAD AND

POWER WIRING

• CONNECT CONTROL POWER

WIRING

START-UP............................................................... 6-8

SERVICE.................................................................. 8-10 '

MAINTENANCE......................................................10-12

SAFETY CONSIDERATIONS

Installation and servicing of air conditioning

equipment can be hazardous due to system pressure
and electrical components. Only trained and quali­
fied service personnel should install, repair or

service air conditioning equipment.

Untrained personnel can perform basic mainte­

nance functions of cleaning coils and filters and re­
placing filters. All other operations should be per­

formed by trained service personnel. When working

on air conditioning equipment, observe precautions

in the literature, tags and labels attached to the unit
and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and

work gloves. U se quenching cloth for brazing opera­
tions. Have fire extinguisher available for all brazing
operations.

INSTALLATION

Step 1 — Check Equipment and Jobsite

UNPACK UNIT — Move to final location. Slide

from carton taking special care not to damage serv­
ice valves or grilles.

INSPECT EQUIPMENT — File claim with ship­
ping company if damaged or incomplete. Check

factory supplied (field installed) liquid line solenoid
valve for shipping damage.

COMPLETE OR CONSIDER SYSTEM RE­
QUIREMENTS before installation;

Consult local building codes and National Elec­

trical

Code

(NEC)

for

special

installation

requirements.

When installing, allow sufficient space for airflow

clearance, wiring, refrigerant piping and service.

Maintain a minimum of 4 ft clearance from obstruc­

tions above and 18 in. on sides of unit. Maintain a

distance of 24 in. between condensing units. Posi­
tion so water from roof or eaves does not flow

directly on unit.

Install on a solid, level mounting pad. It is not

necessary to attach unit to pad but if desired or
required by local code, position tiedown bolts in

pad. Fasten unit to pad using 2 holes provided in

unit base. See Fig. 1.

Carrier Cooling System Capacity Optimization —

AccuRater™ (bypass type) refrigerant control, with

field-replaceable piston (see Fig. 2), is supplied on
evaporator. Use Optimization Chart, Table 2 to
find AccuRater piston size required for condenser/
evaporator system being installed.

© Carrier Corporation 1983

Form 38ED-1SI

Advertising