SUCTION PRESSURE (PS)G)

50

60

Fig. 18 — Heating Cycle Operation Chart

50EQ034

#

Table 7 — Check Valve Functions — 50EQ

CHECK VALVE

IDENTIFICATION

LOCATION

COOLING

CYCLE

HEATING

CYCLE

COOLING CYCLE

CHECK VALVE STUCK

HEATING CYCLE

CHECK VALVE STUCK

A

Outdoor
Coil
Header

Closed

Open

Open

Closed

Open

Closed

Lose
Circuiting

in Outdoor
Coil Acts
like Low
Charge

Normal

Normal

Top 3 Circuits

Restricted

B

Outdoor
Coil
Liquid
Line
Leaving
Coil

Open

Closed

Normal

Restricted
Liquid
Line

Flooding

Outdoor
Coil and
Compressor

Normal

C

Outdoor
Coil
Liquid
Line
Feeding
Capillaries

Closed

Open

Lose Slight

Amount of

Capacity

Normal

Normal

Restricted

Outdoor
Capillaries

D

Indoor
Coil
Liquid
Line
Leaving
Coil

Closed

Open

Bypasses
Coil and
Floods
Compressor

Normal

Normal

Restricted
Liquid Line

E

Indoor
Coil

Header

Open

Closed

Normal

Bottom
Circuits
of Indoor
Coil

Inactive

Lose Indoor
Coil
Circuiting

Symptom of

Low Charge

Normal

F

Indoor
Coil
Liquid
Line
Feeding
Capillaries

Open

Closed

Normal

Restricted
Indoor
Capillaries

Lose
Small

Amount of

Capacity

Normal

#