Troubleshooting guide, Symptom and probable cause, Compressor shuts off, fan overload – Carrier 38VH User Manual

Page 12: Or high pressure switch cut out, or, Internal pressure relief opens, Compressor runs but cooling is insufficient, High suction pressure, Probable remedy, Evaporator fan stopped, Compressor shuts off

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TROUBLESHOOTING GUIDE

SYMPTOM AND

PROBABLE CAUSE

COMPRESSOR SHUTS OFF, FAN OVERLOAD
OR HIGH PRESSURE SWITCH CUT OUT, OR
INTERNAL PRESSURE RELIEF OPENS
Condenser Fan On

1 Condenser air restricted or recirculating

2 Refrigerant overcharge, noncondensables in

system system restricted

3 Improper line voltage, loose electrical connec­

tions, faulty run capacitor

Condenser Fan Off

1 Fan slipping on shaft, fan motor bearing stuck,

fan motor defective.

2 Loose electrical connections Fan motor over­

load open

COMPRESSOR RUNS BUT COOLING

IS INSUFFICIENT

1 Low refrigerant charge.

2 Dirty filters, partially restricts airflow (evaporator

coil may be partially iced).

High Suction Pressure

1. Defective compressor valves (accompanied by

low head pressure)

PROBABLE REMEDY

1 Condenser coil blocked Maintenance, Coil

Cleaning Check airflow clearance (Fig 1)

2 Review Refrigerant Charging procedures, purge

system, replace filter-drier, check refrigerant
control

3 Review Installation, Step 3, replace capacitor

1 Tighten fan hub setscrews, see Condenser Fan

Motor Removal

2 Check unit wiring Check motor bearings Re­

place motor

COMPRESSOR SHUTS OFF FROM
LOW-PRESSURE SWITCH CUTOUT

Evaporator Fan Runs

1 Low refrigerant charge or restricted evaporator

air

2 Restricted refrigerant flow.

Evaporator Fan Stopped

1 Evaporator fan-motor defective or inoperative.

1. Check Refrigerant Charging procedures
2 Check evaporator air system for dirty filters,

obstruction in ductwork, improper damper
settings. Refer to coil, fan coil or furnace

instructions as applicable.

1. Perform Compressor Replacement procedure.

Recheck system charge.

1. See Compressor Runs But Cooling Is Insufficient

above regarding filters, ductwork, etc.

2 Check refrigerant flow device, be sure correct

AccuRater™ orTXV is used.

1. Check furnace or fan instructions regarding de­

fective fan relay, belt adjustment, condition of

motor bearings and overloads, check and tighten
electrical connections, check power supply.

COMPRESSOR SHUTS OFF,
WILL NOT RESTART
Contactor Open

1 Burned out transformer, open thermostat circuit,

faulty control relay, open overload

Contactor Closed or Closes Then Opens

1 Compressor power is out, compressor motor is

burned out or internal overloads are open. Time
Guard® Circuit faulty

Check control circuit components and wiring
Refer to unit label diagram, check all conditions
Refer to Standard System Techniques Manual,
Chapter 2, Electrical

\

Check main power supply wiring Refer to Elec­
trical Data table and label diagram Substitute

Time Guard with a replacement to verify its oper­

ation Refer to Standard Service Techniques
Manual, Chapter 2, Electrical

For replacement items use Carrier Specified Parts.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

3a 2a

Form 38VH-2SI Supersedes 38VFI-1 SI

Printed in USA

3-80

PC 101

Catalog No. 533-830

Advertising