Carrier 19DG User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

AGITATOR VALVE CHECK - The refrigerant

agitator solenoid valve is open when the compres­

sor guide vanes are closed. When opening.the guide
vanes manually in the following procedure, listen
for the sound of the agitator solenoid valve closing
as the vanes reach 20—28 deg of opening.

MOTOR CURRENT CALIBRATION

1. Establish a steady motor current value for this

calibration. Open guide vanes manually (capac­

ity control to “Inc”) until full load current is
reached. Motor current calibration (Eig. 3) may
have to be turned counterclockwise to permit
vanes to open further. Do not exceed 105% of

nameplate full load amperes.

If system load is sufficient to maintain full-load

current for a period of time, calibrate at this
condition. With small loads, pull down to and

maintain (capacity control to “Hold”) design
leaving chilled water temperature and calibrate
at this condition.

2. Measure motor current at selected condition

and determine its percentage of full load motor

current.

3. Use this percentage figure to set the electrical

demand adjustment (Eig. 3) per the following
table:

Setting Operating Controls

Percent of Full

Load Motor Current

105

85 or above

65 to 84

45 to 64

below 45

Electrical

Demand

Adjustment

Setting

100

percent

80 percent

60 percent

40 percent

Control cannot be

calibrated

4. Turn the motor current calibration adjustment

fully clockwise. This will cause the guide vanes
to close part way.

5. Turn thermostat (Eig. 3) to “Cooler” (fully

counterclockwise).

6. Set capacity control to “Inc” position.

7.

Slowly turn the motor current calibration

counterclockwise. Allow the guide vanes to
open until motor current reaches 5% above the
electrical demand setting.

NOTE: There is a time lag of several seconds
due to feedback capacitance in the motor

current circuit. When the motor current
calibration setting is adjusted, allow for this

time lag.

8. Check the foregoing motor current calibrations

with

machine

under

“Auto.”

control

as

follows:

a. Close vanes manually (capacity control to

“Dec”).

b.

Turn capacity control to “Auto.” Vanes

should stop opening at electrical demand
setting.

9. If control was calibrated at less than 100% load,

turn electrical demand adjustment setting to

100%. Control is now automatically calibrated

for 100% full load motor current.

This is a two-step motor current limiting

circuit. At 100% full load motor current, the

vanes will stop opening further. If the motor

current should increase to 105% due to some
change in load conditions, the vanes will close

until the motor current is reduced to about

102%. If the motor current is reduced to 98%

or below, the control will respond to leaving

chilled water temperature. The electrical de­
mand adjustment allows the operator to reduce
the maximum current drawn by the motor,
minimizing the electrical demand rate during
off-season operation.

If control cannot be calibrated with above
procedure, check voltage signal from signal
resistor in starter. At 100% full load current,
voltage between terminals 23 and 24 inside

control panel must be 0.5 ± 0.1 volts. If not in
this range, check sizing of resistor in starter.

CHILLED WATER CALIBRATION

1. Turn throttle range adjustment (Eig. 3) fully

clockwise.

2. Turn chilled water thermostat (Eig. 3) until

design chilled water temperature is maintained.
Mark thermostat at this position. If capacity

control vanes hunt, turn throttle range adjust­
ment counterclockwise in small increments
until hunting ceases. Chilled water thermostat
may require resetting.

TRIMMING REERIGERANT CHARGE - After
the machine has been placed in operation, it may
be necessary to adjust the refrigerant charge for
optimum machine performance.

When machine full load is available, add refrig­

erant slowly until the difference between the
leaving chilled water temperature and the cooler
temperature reaches design conditions or becomes
a minimum. Shut the machine down and allow the
refrigerant to drain to the cooler. Mark the level at
the bull’s-eye glasses on the float chamber and
maintain that shutdown refrigerant level.

Advertising