Temperature-pressure relief valve, Warning, Temperature-pressure relief valve ,11 – Sears KENMORE POWER MISER 153.336431 User Manual

Page 10: Installing the new water heater, Water piping

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Installing the New Water Heater

Water Piping

-WARNING

HOTTER WATER CAN SCALD: Water heaters are intended to
produce hot water. Water heated to a temperature which
will satisfy clothes washing, dish washing, and other sanitiz­
ing needs can scald and permanently injure you upon con­

tact. Some people are more likely to be permanently injured

by hot water than others. These include the elderly, children,

the infirm, or physically/mentaify handicapped. If anyone

using hot water in your home fits into one of these groups or
if there is a local code or state law requiring a certain tem­
perature water at the hot water tap, then you must take spe­

cial precautions. In addition to using the lowest possible tem­
perature setting that satisfies your hot water needs, some

type of tempering device, such as a mixing valve, should be
used at the hot water taps used by these people or at the
water heater. Mixing valves are available at jilumbing supply
or hardware stores. Follow manufacturers instructions for
installation of the valves. Before changing the factory setting
on the thermostat, read the “Temperature Regulation" section
in this manual.

This water heater shall not be connected to any heating
systems or component(s) used with a non-potable water
heating appliance.

NOTE: To protect against untimely corrosion of hot and
cold water fittings, it is strongly recommended that di­

electric unions or couplings be installed on this water
heater when connectea to copper pipe.

The illustration shows the attachment of the water piping
to the water heater. The water heater is equipped with %

inch water connections.

NOTE: If using copper tubing, solder tubing to an

adapter before attaching the adaptor to the coH water
inlet connection. Do not solder the cold water supply
line directly to the cold water inlet. It will harm the dip
tube and damage the tank.

1. Look at the top cover of the water heater. The water

outlet is marked hot. Put two or three turns of teflon

tape around the threaded end of the threaded-to-sweat

coupling and around both ends of the threaded nip­
ple. Using flexible connectors, connect the hot water
pipe to the hot water outlet on the water heater.

INSTALLATION COMPLETED USING

SEARS INSTALLATION KIT

HOT OUTLET

FLEXIBLE WATER

SHUTOFF

VALVE

2. Look at the top cover of the water heater. The cold

water inlet is marked cold. Put two or three turns c
teflon tape around the threaded end of the threadeo
to-sweat coupling and around both ends of the ¥

4

threaded nipple. Using flexible connectors, connect

the cold water pipe to the cold water inlet of the water
heater.

NOTE: This water heater is super insulated to mini­
mize heat loss from the tank. Further reduction in

heat loss can be accomplished by insulating the hot

water lines from the water heater.

Temperature-Pressure Relief Valve

--------------------------WARNING----------------------------

At the time of manufacture this water heater was equipped
with a temperature-pressure relief valve. For protection
against excessive pressures and temperatures in this water
heater, install temperature-pressure protective equipment

required by local codes, but not less than a combination

temperature-pressure relief valve certified by nationally
recognized testing laboratory that maintains periodic
inspection of production of listea equipment or materials, as
meeting the requirements for Relief Valves and Automatic
Gas Shutoff Devices for Hot Water Supply Systems, the
latest edition ANSI Z21.22. This valve must be marked with
a maximum set pressure not to exceed the marked
hydrostatic working pressure of the water heater (150
Ibs./sq. in.). The relief valve must be marked with

e

discharge capacity not less than the water heater Btu input
rate as shown on the model rating plate.
Install the temperature-pressure relief valve directly into the

fitting of the water heater. Position the valve downward and
provide tubing so that any discharge will exit only within 6
inches above, or at any distance below the structural floor.
Be certain that no contact is made with any live electrical
part. The discharge opening most not be blocked or reduced
in size under any circumstances. Excessive length, over 15

feet, or use of more than two elbows can cause restriction
and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the

relief valve and the tank. Do not connect tubing directly to
discharge drain unless a 6” air gap is provided. To prevent
bodily injury, hazard to life, or damage property, the relief
valve must be allowed to discharge water in quantities

should circumstances demand. If the discharge pipe is not

connected to a drain or other suitable means, the water

flow may cause property damage.
The Discharge Pipe:
-Must not be smaller in size than the outlet pipe size of the

valve, or have any reducing couplings or other restriction.

-Must not be plugged or blocked.
-Must be of material listed for hot water distribution.
-Must be installed so as to allow complete drainage of both

the temperature-pressure relief valve, and the discharge

pipe.

-Must terminate at an adequate drain.
-Must not have any valve between the relief valve and tank.

If the water heater is installed using a check valve in th

water line or a water meter with a check valve, contac,

the local utility or local Sears Service Center on how to

control this situation.

10

Advertising