If local codes do not permit the connection of a neutral ground wire to the neutral wire,
see "Optional 3-wire connection" section in "Electrical Connection - U.S.A. Only"
section.

■ A 4-wire power supply connection must be used when the appliance is installed in a

location where grounding through the neutral conductor is prohibited. Grounding

through the neutral is prohibited for (1) new branch-circuit installations, [ 2 ) mobile

homes, (3) recreational vehicles, and (4j areas where local codes prohibit grounding

through the neutral conductors.

If using a power supply cord:

Use a UL listed power supply cord kit marked for use with clothes dryers. The kit should

contain:

■ A Ul. listed 30-amp power supply cord, rated 120/240 volt minimum. The cord should be

type SRD or SRDT and be at least 4 ft (1.22 m) long. The wires that connect to the dryer

must end in ring terminals or spade terminals with upturned ends.

■ A UL listed strain relief.

If your outlet looks like this:

If connecting by direct wire:

Power supply cable must match power supply (4-wire or 3-wire) and be:

Flexible armored cable or nonmetallic sheathed copper cable (with ground wire),
protected with flexible metallic conduit. All current-carrying wires must be insulated.

1 0-gauge solid copper wire (do not use aluminum).

■ At least 5 ft (1.52 m) long.

4-wire receptacle (14-30R)

Then choose a 4-wire power supply cord with ring or spade terminals and Ul., listed strain

relief. The 4-wire power supply cord, at least 4 ft (1.22 m) long, must have four 10-gauge

copper wires and match a 4-wire receptacle of NEMA Type 14-30R. The ground wire (ground
conductor) may be either green or bare. The neutral conductor must be identified by a white
cover.

If your outlet looks like this:

3-wire receptacle (10-30R)

Then choose a 3-wire power supply cord with ring or spade terminals and Ul. listed strain

relief. The 3-wire power supply cord, at least 4 ft (1.22 m) long, must have three 10-gauge

copper wires and match a 3-wire receptacle of NEMA Type 1 0-30R,

GROUNDING INSTRUCTIONS

® For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer uses a cord having an equipment-grounding
conductor and a grounding plug. The plug must be plugged
into an appropriate outlet that is properly installed and
grounded in accordance with all local codes and ordinances.

■ For a permanently connected dryer:
This dryer must be connected to a grounded metal,
permanent wiring system, or an equipment-grounding
conductor must be run with the circuit conductors and
connected to the equipment-grounding terminal or lead on
the dryer.

WARNING:

Improper connection of the equipment­

grounding conductor can result in a risk of electric shock.
Check with a qualified electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug on the power
supply cord: if it will not fit the outlet, have a proper outlet
installed by a qualified electrician.

SAVE THESE INSTRUCTIONS