With Smart Recovery selected (factory default), transition out of
setback begins a fixed time period before selected recovery time
and gradually adjusts room temperature so desired temperature
will be achieved at selected recovery time. The fixed time period
is 1.5 hours. It operates in both heating and cooling. This only
applies to programmable operation.

Media Filter

If a media filter is installed in the indoor unit, the system will
perform a static pressure check of the system whenever power is
applied to the system, or the system is transitioned from Off to
Cool or Heat modes. The blower will run at a medium airflow for
one minute.

TrueSense™ Dirty Filter Detection

When MEDIA or MEDIA+EAC is installed, a static pressure
check will automatically be performed every 24 hours at 1:00PM
to monitor filter accumulation.

TROUBLESHOOTING

Infinity Control™ does not power up.

1. Recheck wiring to ABCD on all devices.

2. Make sure all colors match for every terminal.

3. Make sure power is applied to the indoor unit, and the amber

LED is lit on indoor control circuit board.

4. Check for 24VAC between the C and D terminals at Infinity

Control™ terminal connector.

5. Check fuse on indoor unit’s circuit board.

Display says

Indoor Unit Not Found

1. Recheck wiring to ABCD on all devices.

2. Make sure all colors match for every terminal.

3. Press left-side button to try again.

4. If display still reads

″Indoor Unit Not Found″, disconnect all

devices from ABCD and connect User Interface directly to
indoor unit.

Display says

Outdoor Unit Not Found, and I have a two-

speed communicating outdoor unit:

1. Recheck wiring to ABCD connector on outdoor unit.

2. Make sure all colors match for every terminal.

3. Check for 24VAC between the C and D terminal connector.

I made a mistake on the start-up screens, and hit the right-side
button to get to the run mode. How do I get back to start-up?

1. Press the ADVANCED button for at least 10 seconds.

2. Install/Service menu will appear.

3. Scroll down to the INSTALL selection.

4. Press the right-side button; the screen will prompt you to press

the right side again to re-install the system.

CRITICAL ALERT SCREEN

The following errors will cause a Critical Malfunction screen to
pop up. Heat and Cool LEDs will alternately flash at a 1 second
rate.

FAN COIL

Code 44 - Motor Communication Fault

Code 41 - Blower Motor Fault

FURNACE

Code 15 - Blower Motor Lockout

Code 22 - Abnormal Flame Proving Signal (not dual fuel)

Code 41 - Blower Motor Fault

USER INTERFACE

No communication with indoor unit

SYSTEM MALFUNCTION SCREEN

The following errors will cause a System Malfunction Screen to
pop up:

FAN COIL

Code 37 - Heater output sensed ON when not energized

FURNACE

Code 13 - Limit Circuit Lockout

Code 14 - Ignition Lockout

Code 21 - Gas Heating Lockout

Code 22 - Abnormal Flame Proving Signal (dual fuel only)

Code 23 - Pressure Switch Did Not Open

Code 24 - Secondary Voltage Fuse Open

Code 33 - Limit Circuit Fault AND High Heat Only is active

Code 45 - Control Circuitry Lockout

NOTE:

For all the above furnace error codes, the system will use

heat pump heating exclusively if available. When the error code is
cleared or disappears, furnace heating will resume.

TWO-SPEED OUTDOOR UNIT

Code 85 - VC voltage at standby

Code 86 - High capacity compressor lockout

USER INTERFACE

Temp Sensor Failed,

″NO SENSOR DATA″ shown in place of

actual temp.

Outdoor Unit communication fault.

Network Interface Module (NIM) communication fault

Defrost Error (defrost signal on for more than 15 minutes)

The user can press the right side button to dismiss the notice. The
regular run mode screen will then appear except

″SYSTEM

MALFUNCTION

″ will appear in place of the day/time. If the error

has not disappeared within 24 hours, the above display will return.
If the error code disappears,

″SYSTEM MALFUNCTION″ will

disappear and the day/time will reappear.

71

˚

FAN: AUTO

CALL TECHNICIAN

OUTSIDE: 94

o

ALERT !

C

RITICAL MALFUNCTION

HVAC SERVICE

1 800 555-1212

Fig. 26 — Critical Alert Screen

A04027

FAN: AUTO

CALL TECHNICIAN

OUTSIDE: 94

o

SYSTEM MALFUNCTION

HVAC SERVICE

1 800 555-1212

DISMISS

NOTICE >

71

˚

Fig. 27 — System Malfunction Screen

A04028

Copyright 2004 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231

uid01-1si

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

misc. misc.

PC 101

Catalog No. 809-50020

Printed in U.S.A.

Form UID01-1SI

Pg 12

01-04

Replaces: NEW

Advertising