Carrier Infinity SYSTXCCUID01 User Manual

Page 9

Advertising
background image

SETUP = FAN COIL:

HP/AC AIRFLOW:

COMFORT (default)

EFFICIENCY

MAXIMUM

Selects the airflow of the fan coil when heating or cooling with a
heat pump (or cooling with an AC unit). COMFORT is a
decreased airflow used to improve humidity control. EFFI-
CIENCY
is the airflow used to meet specified ratings. MAXI-
MUM
is a fixed airflow speed of 400 CFM/ton based on the
outdoor unit size.

DEHUM AIRFLOW:

NORMAL (default)

HIGH

Normal airflow adjustment used during dehumidifying. If duct
sweating is an issue, selecting HIGH will increase the dehumidi-
fying airflow speed and reduce the sweating.

HEATER SIZE:

(choices dependent upon fan coil model)

This will show the heater size entered during the start-up process.
This value can be changed to another value (limited by the model
of the fan coil). If the electric heater is self-identifying, this value
is not shown.

SETUP = HEAT PUMP / AC:

COOLING LOCKOUT:

NONE (default)

45° F.

50° F.

55° F.

Outside temperature below which cooling will not be provided.

ENTERED SIZE:

(dependent on indoor unit model)

Size of the outdoor unit entered during the start-up process. If the
outdoor unit is a communicating model, this value will not be
shown. This size can be changed here but is limited to sizes that the
indoor unit can handle.

DEFROST INTERVAL:

30 minutes

60 minutes

90 minutes (default)

120 minutes

Time interval at which defrost cycles can occur on a heat pump.

ELECT HEAT LOCKOUT:

NONE (default)

+5 to 55 deg. F

Outside temperature above which the electric heat will not operate.

HIGH COOL LATCH:

NONE (default)

80 - 110 deg F

Outside temperature above which only the high speed (of a
2-speed outdoor unit) will run when cooling.

SETUP = ACCESSORIES

FILTER TYPE:

MEDIA

EAC

MEDIA+EAC

CLEAN INTERVAL: 30 to 180 days (of blower operation).
(Default = 90)

Interval at which the Clean Filter notification will turn on. Applies
to EAC or MEDIA+EAC filter selection only.

SETUP = HUMIDIFIER

HUMIDIFIER INSTALLED:

NO

YES

If YES, indicates to the system whether a humidifier is installed
and enables humidification functions.

CHANGE PAD INTERVAL: 1 to 24 months of humidifier
operation (default=6 months)

Interval at which the Change Humidify Pad notification will be
displayed.

HUMIDIFY WITH FAN:

NO (default)

YES

If YES, the humidifier will run with Continuous Fan if there is a
humidify demand.

SETUP = VENTILATOR

NOTE:

Only appears if ventilator is installed.

CLEAN INTERVAL:

60 to 180 days of operation (default=90)

Interval at which the Clean Ventilator Pre-filter notification will
turn on.

SETUP = UV LIGHTS

UV LIGHTS INSTALLED:

NO

YES

If YES, indicates to the system whether UV lights are installed.

CHANGE INTERVAL:

6 to 48 months operation time (default=12 months)

Interval at which the Change UV Lights notification will be
displayed.

SETUP = SYSTEM MAINTENANCE

REMIND OWNER OF ROUTINE MAINTENANCE EVERY:

This setup is used to adjust the timer interval in which the normal
System Maintenance notification is turned on for the homeowner.

Range= OFF, 6 to 24 months, (default=12)

9