Louisville Tin and Stove BFT201 User Manual

Page 5

Advertising
background image

STEP 4. Compare the total Btu the area can support (from Step 2) to the total Btu in the area the heater will be installed
(from Step 3). If the total from Step 2 is larger this is considered an unconfined space, if Btu total from Step 3 is larger this
is considered a confined space and provisions must be made for additional combustion and ventilation air. EXAMPLE:
Btu area can support is 56,250, total Btu in area is 106,000 – this would be a confined space.

NOTE: A third construction class is one with unusually tight construction, defined as, construction where: (A) Walls
and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of 1 per (6x10-11 Kg
per pa-sec-m²) or less with openings gasketed or sealed, and, (B) Weatherstripping has been added enable windows and
doors, and , (C) Caulking or sealants are applied to areas such as joints around window and door frames, between sole
plates and floors, between wall ceiling joints, between wall panels, at penetration for plumbing, electrical, and gas lines,
and at other openings.

WARNING: If the area in which the heater may be operated does not meet the required volume for indoor combustion
air, combustion and ventilation air shall be provided by one of the methods described in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Air for Combustion and Ventilation, the International Fuel Gas Code, or applicable local codes.”
Examples would be to provide two permanent openings either to an adjoining room, or to the outside. See the National
Fuel Gas Code
for details. See Figure 9 & Figure 10 below.

FRESH AIR FOR COMBUSTION, VENTILATION AND HEAT DISTRIBUTION - CONT’D.

INSTALLATION

Installation and service must be performed by a qualified installer, service technician or the gas supplier.

LOCATION

1)

For most efficient performance, locate heater as centrally as possible in the area to be heated.

2)

Do not install heater in a closet, alcove or small hallway where the heater could be isolated from the space to be
heated and adequate combustion air by closing a door.

Page 5

Chimney or gas vent

Opening

Opening

Equipment located in confined
spaces; all air from inside the
building. See 5.3.3(a).

Furnace Water

Heater

FIGURE 9

Chimney or gas vent

Water
Heater

Furnace

Ventilation louvers
(each end of attic)

Outlet Air

Inlet Air

Alternate
air inlet

Ventilation louvers for
unheated crawl space

Equipment located in confined spaces; all air from
outdoors - inlet air from ventilated crawl space and
outlet air to ventilated attic. See 5.3.3(b).

FIGURE 10

Advertising
This manual is related to the following products: