Installation – Desa SVYD18PRA User Manual

Page 13

Advertising
background image

www.desatech.com

113084-01E

13

INSTALLATION

Continued

CAUTION: Avoid damage to

regulator. Hold gas regulator

with wrench when connecting it

to gas piping and/or fittings.

* Purchase the optional CSA design-certified

equipment shutoff valve from your dealer. See

Accessories, page 27.

** Minimum inlet pressure for purpose of input

adjustment.

Figure 16 - Gas Connection

(SVYD18PRA/NRA Series)

3” Min

Sediment Trap

Gas Control

CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*

Approved
Flexible
Gas Hose (if
allowed by
local codes)

Cap Pipe Tee
Nipple Joint

PROPANE/LP

From External
Regulator
(11" W.C. to 14"
W.C. Pressure)

NATURAL

From Gas
Meter (5” W.C.
to 10.5” W.C.
Pressure)

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.

cAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply and

heater. See guidelines under Con-

necting to Gas Supply, page 11.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1. Disconnect appliance with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

heater regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

4. Check all joints of gas supply piping system.

Apply a noncorrosive leak detection fluid to

gas joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Reconnect heater and equipment shutoff

valve to gas supply. Check reconnected fit-

tings for leaks.

Test Pressures Equal To or Less Than 1/2
PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 17).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter for natural

or propane/LP supply to equipment shutoff

valve (see Figure 18 or 19, page 14). Apply a

noncorrosive leak detection fluid to gas joints.

Bubbles forming show a leak.

4. Correct all leaks at once.

Figure 17 - Equipment Shutoff Valve

Equipment
Shutoff Valve

Closed

Open