Austin Hughes Fan Unit & ICM-02 User Manual

Page 23

Advertising
background image

www.austin-hughes.com

UM-ICM-02-Q215V1

P.18

< 2.5 > Daisy Chain Connection

Using the dip switch no. 1, 2, 3, 4, 5, 6 & 8 to setup each FAN unit level as below :

Cascaded FAN units

Dip switch no.

1

2

3

4

5

6

8

1st level

Master IP

Fan Unit Model

On

On

On

On

On

On

Off

2nd level Remote Fan Unit Model

Off

On

On

On

On

On

Off

3rd level Remote Fan Unit Model

On

Off

On

On

On

On

Off

4th level Remote Fan Unit Model

Off

Off

On

On

On

On

Off

5th level Remote Fan Unit Model

On

On

Off

On

On

On

Off

6th level Remote Fan Unit Model

Off

On

Off

On

On

On

Off

7th level Remote Fan Unit Model

On

Off

Off

On

On

On

Off

8th level Remote Fan Unit Model

Off

Off

Off

On

On

On

Off

9th level Remote Fan Unit Model

On

On

On

Off

On

On

Off

10th level Remote Fan Unit Model

Off

On

On

Off

On

On

Off

11th level Remote Fan Unit Model

On

Off

On

Off

On

On

Off

12th level Remote Fan Unit Model

Off

Off

On

Off

On

On

Off

13th level Remote Fan Unit Model

On

On

Off

Off

On

On

Off

14th level Remote Fan Unit Model

Off

On

Off

Off

On

On

Off

15th level Remote Fan Unit Model

On

Off

Off

Off

On

On

Off

16th level Remote Fan Unit Model

Off

Off

Off

Off

On

On

Off

Daisy chain level setting

ON

OFF

** No. 7 dip switch only for audio alarm setting

Steps :

Only

Master IP

fan unit built-in IP remote access module.

Master IP

fan unit MUST be set on the 1st daisy chain level according to the table below.

For the 2nd - 16th levels ( remote fan unit models ), please make the level setting according to the table below.

For the cabling connection, please refer to the next page.

Advertising