Replacement, removal or addition for remote FAN unit

3.

How to move out a remote fan unit ( without a replacement ) ?

Step 1

- Prepare an appropriate length Cat. 5 / 6 cable.

Step 2

- Click Disable monitoring in <Details> page to stop monitoring the removed remote

fan unit.

Step 3

- Use the Cat. 5 / 6 cable to bridge over the removed remote fan unit to minimize

log / data loss.

Step 4

- Power off & remove the fan unit from connection.

If the removed remote fan unit NOT in the last level, you MUST reconfi gure and reset the

level for the affected remote fan unit(s) which next to the removed remote fan unit.

Ignore step 1 & 3 if the removed fan unit is in the last level.

4.

How to add an extra remote fan unit to an existing fan unit group ?

Step 1

- Prepare a new remote fan unit and set the remote fan unit level accordingly.

( Please refer to user manual < 2.5 > for the fan unit level setting )

Step 2

- Prepare an appropriate length Cat. 5 / 6 cable.

Step 3

- Click Set maintenance in <Details> page for the affected remote fan unit(s) which

next to the added remote fan unit.

Step 4

- Install, connect and power on the new remote fan unit.

Step 5

- Reconfi gure & reset the level for the affected remote fan unit(s) which next to the

added remote fan unit.

Step 6

- Click Remove maintenance in <Details> page for the affected remote fan unit(s).

Step 7

- Click Search in <Status> page to search the new installed remote fan unit.

Step 8

- Confi gure the new remote fan unit in <Details> & <Temp. sensor> page

such as Rack, Position, Alarm Temp...

Ignore step 3, 5 & 6 if the added remote fan unit is in the last level.