Water Connections

W

ATER

I

NSTALLATION

A permanent water supply is required to be connected to the unit. Units have been type
test certified to MP52, Spec101. Certificate No.8663.

Connecting the Water Supply

• The water supply pipe work and connection

to the air conditioner must be installed by a
licensed plumber and conform to AS 3500,
state & local plumbing regulations.

• Ensure water pressure to the appliance does

not exceed the maximum static pressure of
500kPa (50 m head) as per As 3500 (section
3.3)

• The ball valve connection is inside the unit.

Ensure the copper inlet pipe is secured to
prevent movement of the float valve.

• The supply pipe should be 12mm copper pipe or similar approved. A ¼ turn ball

isolating valve must be installed on the supply pipe near the unit for ease of
maintenance. Do not use duo or non-return valves of any kind including stop taps
with jumper washer.

NOTE: Non return type valves can have and effect on the operation of the

water solenoid valves. Lock up and damage can be caused.

• Fit water supply tap close to the unit to assist in routine servicing.

• Before connecting the supply pipe flush it of any swarf or debris that may cause the

float valve to leak.

NOTE: In areas where water pipes freeze, provisions will be needed to drain

the water piping to prevent damage to the air conditioner.