Commissioning

F

AN

O

PERATION

• Check that pulleys are correctly aligned.

• Check the belt tension is correct. Nominally 15

– 20mm depression.

• Check bearings are tight on shaft

• Set the fan running and check.

• Check that the air is being evenly distributed

through the ductwork.

• Make adjustments, as required, to any manual

air dampers that may be fitted.

Fan Motor Current. Check the motor

operating current is not greater the rating plate
value.

o

For systems with high statics and

non standard drive check motor
current. Where required, review
pulley requirements relative to the
system static. Where variable pitch
pulleys are fitted adjust accordingly.

o

For systems with minimal static eg

straight dropper and plenums,
check motor current. A smaller
motor pulley to standard may be
required.

C

ONTROLS

Check all control functions are working

C

USTOMER HAND

O

VER

Instruct the customer in the use of the product.

• Controls

• Bleed

off

• Venting the air via the side of the premises the wind is not blowing from.

• Maintenance

Requirements

Hand over of the customer’s operational manual.

Page 17