Attempt to go beyond extend limit

This parameter error will occur whenever either a

Go

or

Relative Move

command

requests that the axis moves to a position beyond the

EXTEND LIMIT

. The

COMMAND POSITION

will be set to the

EXTEND LIMIT

. The move will continue if

the bits for the Parameter Error are cleared in the

AUTO STOP

word. To remedy this

problem:

•

Fix the control program to avoid issuing illegal commands.

•

If the

EXTEND LIMIT

is set incorrect, fix its value.

Attempt to go beyond retract limit

This parameter error will occur whenever either a

Go

or

Relative Move

command

requests that the axis moves to a position beyond the

RETRACT LIMIT

. The

COMMAND POSITION

will be set to the

RETRACT LIMIT

. The move will continue if

the bits for the Parameter Error are cleared in the

AUTO STOP

word. To remedy this

problem:

•

Fix the control program to avoid issuing illegal commands.

•

If the

RETRACT LIMIT

is set incorrect, fix its value.

Requested drive too large

This parameter error indicates that requested drive used by either an

Open Loop

command or a move command using

Quick Mode

is too large. The maximum allowed

drive is ±12000 millivolts, although values this large can easily cause an

Overdrive Error

.

Invalid command value

This parameter error is set if either the Integral Drive or Null Drive is set to a value

greater than ±10000 with the

Set Integral Drive

and

Set Null Drive

commands.

Invalid step number given in "Start Events" command

Because there are only 256 event steps—numbered 0 to 255—any

COMMAND VALUE

outside of that range with the

Start Events

command will generate this error.

Invalid scale value

This parameter error indicates that a

SCALE

was set to an invalid value: either 0 or

32768. If you are having a difficult time setting the

SCALE

parameter, you may want to

try

using the Scale/Offset Calibration Utilities

.