Table 2 - equivalent length chart, Figure 3 – DuraVent FasNSeal 8090 Installation User Manual

Page 4

Advertising
background image

4

should include maximum number of elbows
and related pressure-drops. The total vent
length from the appliance to the termination
should not be greater than the maximum

Figure 2

CAT I EXHAUST

PATH

CAT IV EXHAUST

PATH

other approved factory built vent), special
care must be taken. Prior to reline work
being started:

Ensure the new proposed vent system
is appropriate for the two appliances in
question. For the Category IV appliance,
reference the OEM Appliance manual for
information on min/max vent run and vent
diameter requirements. OEM guidance

TERMINATION

CAP

CAP MOUNT

STRAPS /

HARDWARE

FNS FLEX

COLLAR

CAT IV

FIRESTOP /

HARDWARE

B VENT

PRE-EXISTING

CATEGORY

IV EXHAUST

ENTRY

CAT I

EXHAUST

ENTRY

POLYPRO

TO FNS FLEX

ADAPTER

Figure 3

FNS FLEX

FIG.5

BIRDSCREEN

Table 2 - Equivalent Length Chart

2" Equivalent Length 3" Equivalent Length

4" Equivalent Length

5" Equivalent Length

1-ft Rigid Pipe

1-ft

1-ft

1-ft

1-ft

1-ft SS FNS (or
Secure Seal)Flex

Same as rigid pipe (or

elbows)

Same as rigid pipe (or

elbows)

Same as rigid pipe (or

elbows)

Same as rigid pipe (or

elbows)

1-ft Flex Pipe

0.4-ft

(updsized one diameter)

0.6-ft

(updsized one diameter)

0.6-ft

(updsized one diameter)

N/A

45 Elbow

3-ft

3-ft

5-ft

6-ft

90 Elbow

5-ft

7-ft

12-ft

14-ft

Tee

9-ft

12-ft

19-ft

21-ft