Echelon Neuron User Manual
Page 162

154
Project Make Errors (PMK)
PMK#
Description
119
Cannot determine default firmware version for image <image>: <failure
reason> [PMK#119]
Failure to determine the firmware version to use as a default. The file
'default.ver', normally contained in the \Lonworks\images folder (on
whichever drive your LonWorks folder resides) could be missing or could be
corrupt. As a workaround, you can explicitly specify the firmware version
in the target device preferences, do not use 'Default' as a firmware version.
120
Cannot determine set of standard libraries from <liblistfile>: <failure reason>
[PMK#120]
Failure to determine standard neuron libraries from <liblistfile>. Verify
that <liblistfile> (a text file), which defaults to
\Lonworks\images\Stdlibs.lst, is present and is not corrupt.
121
Cannot determine transceiver type. Verify preferences in device template and
project. [PMK#121]
Failure to determine the transceiver type. The project file and/or device
template file might be corrupt. Edit these files and correct the transceiver
preferences, specifying an explicit transceiver type (other than 'Default'), if
needed.
122
Cannot calculate signature, <detail> [PMK#122]
The external interface signature cannot be calculated. This indicates
missing or corrupt intermediate files (.BIF and .BF2 extensions), or missing
or corrupt explicit XIF appendix files (XF2 extension). Verify the project
and device preferences, and attempt to build unconditionally.
124
Unknown macro switch record <record> received from <source> (try performing
unconditional build). [PMK#124]
Internal error: switch uses invalid macro value. To fix, attempt the "clean"
and "build unconditionally" commands and
125
Cannot compute dependency code for DRF catalog <catalog> and program ID
<id> (LDRF error <code>). Verify that your LDRF catalog is valid and up-to-
date. [PMK#125]
The LDRF catalog cannot be accessed. Use the Resource Editor utility to
make sure the catalog file is present and intact. The catalog file defaults to
LonWorks\Types\ldrf.cat (on whichever drive your LonWorks folder
resides). If the catalog file is missing, attempt to re-create one by using the
MKCAT.EXE utility, that is available for download from the
126
Malformed min/max model number specified in <file>. Correct preferences or
disable automatic program ID management. [PMK#126]
The program ID data given in the NB device template file <file> appears
malformed. Edit and correct the preferences using NodeBuilder's device