LNS Programmer's Guide

208

Property Name

Description

UseBoundUpdates

If set to True, this property enables implicit binding.

With implicit binding enabled, LNS will attempt to

create connections without user intervention. Changing
this option through the CurrentOptions property does

not have an effect.

Before using this property, you should review the Using

Network Variable Monitor Points section, which
describes different ways you can use implicit binding.

This property must be set to False for temporary monitor

sets and points.

Default Value: False

NOTE: In the

NvMonitorOptions

object accessed through the

DefaultOptions

property of a network variable monitor point, the

PollInterval

and

ThrottleInterval

properties will initially be set to

lcaDefaultMcpInterval (-1)

.

The

GenerateInitialFetch

,

ReportByException

,

ResetPollingIfUpdated

, and

SuppressPollingIfBound

properties will be initially set to

lcaDefaultMcpOption(-

1)

. This causes the values of those properties to always match the corresponding value

stored in the monitor set’s

NvOptions

object. As noted previously, the values of all the

other properties of the monitor set’s

NvOptions

object are only applied to monitor points

as they are added to the set, and so changes to the monitor set’s

NvOptions

object are

not retroactively applied to the monitor points already contained in the set for any other

properties.

Message Monitor Point Options

To recap the previous discussion in this chapter, you should follow these steps when

setting the monitoring options for your message monitor points:

1. Set the defaults for the monitor set by writing to the

MsgOptions

property of the

MonitorSet

object. The following code sample sets the

default values for the

FilterByCode

, and

FilterBySource

properties.

Dim MsgMonitorPointOptions As LcaMsgMonitorOptions
Set MsgMonitorPointOptions = MyMonitorSet.MsgOptions
MsgMonitorPointOptions.FilterBySource = True
MsgMonitorPointOptions.FilterByCode = True
Set MyMonitorSet.MsgOptions = MsgMonitorPointOptions

For descriptions of the properties of the

MsgMonitorOptions

object, see

MsgMonitorOptions Object on page 209.

2. If you do not want a message monitor point in the monitor set to use the

default options established in step 1, set its defaults by writing to the
message monitor point’s

DefaultOptions

property. Note that these

changes will not be applied to a monitor point that is in an open monitor
set until the monitor set is closed and re-opened.

Echelon recommends that you set the DefaultOptions property in the

same transaction that you create the message monitor point whenever

possible. The following code sample sets the default values for a message