2.0 Operation

2.0 Operation

TDX-Series Unit can be of single or multi-channel configuration. Each unit monitors the gas concentration at a single
remote location and consists of a sensor, transmitter. The sensor/transmitter without local read out can be connected to
a controller module via 2-conductor shield cable. The transmitter converts the direct output signal of the sensor into a
standard 4-20mA DC signal. The sensor/transmitter is mounted at a strategic location to monitor the designated
hazardous gas in ambient air.

3.0 Description of Components

3.0 Description of Components

3.1 Description of Sensor

Sensor:

The sensor consists of an electrochemical cell. As the designated gas passes through the cell
membrane, it reacts with the electrolyte to produce a small electrical current proportional to the
partial pressure of gas in the area.

3.2 Description of Transmitter

Cover Screws:

These screws fasten the face cover to the transmitter unit. Face cover must be removed for
installation or for performing calibration adjustments.

Cable Entry:

This fitting provides strain relief entry for cable from the controller module.

Zero Adjust screw: This screw is used to adjust the zero setting during calibration.

Span Adjust screw: This screw is used to adjust the sensitivity during calibration.

Terminal Strip:

This terminal is used to connect the 24VDC power from a controller unit. (See installation for
proper wiring.)

Figure 1: Sensor/Transmitter Module Diagram

Cable Entry

Terminal
Strip

Sensor

PCB

TCX-Transmitter

Multimeter Range:
40 to 200 mV
40mV = 4mA
200mV = 20mA

Zero Adjust Screw

Span Adjust Screw

V+ (24VDC)

V– (24VDC)

V+

V–

(PT+)

(PT–)