0 calibration of the tdx-series unit – ENMET TDX Series User Manual

Page 6

Advertising
background image

ENMET Corporation

TDX-Series

4

5.0 Calibration of the TDX-Series Unit

5.0 Calibration of the TDX-Series Unit

5.1 Checking Channel Response to Gas

The TDX system is supplied precalibrated. After initial installation, the sensor should be checked with calibration/test
gas to confirm gas response. This test should be performed periodically (once every 3 – 4 months).

To check if the sensor requires calibration, introduce an appropriate calibration gas (gas of known concentration) to the
sensor. If there is a discrepancy of more than 10% between the voltage reading on the transmitter and the known
concentration of the gas, then the transmitter should be recalibrated.

Figure 3: Calibration Diagram

TDX-Transmitter

TDX-Sensor

Calibration

Adapter

Flexible
Tubing

Apply Calibration Gas