4.0 Installation of the TDX-Series Unit

4.0 Installation of the TDX-Series Unit

When determining locations for sensor/transmitter to a controller module, keep in mind the following:

Maximum distance between sensor/transmitter and controller module is 3200 ft.

N

OTE

:

Recommend transmission cable between transmitter and controller module to be AWG18 or equivalent, 2 core
shielded cable type. To accommodate a 4-20mA signal at 24VDC.

A wiring diagram for sensor/transmitter to controller module is shown in Figure 2.

A Dimensional Diagram is shown in Figure 2a.

After system is properly installed and power applied, allow 2 hours for warm up and stabilization, then proceed to
verify calibration.

Figure 2a: Mounting Dimensions Diagram

Figure 2: System Wiring Diagram

3.03

76.96

3.03

76.96

+ 24 VDC

– 24 VDC

To Controller

2-conductor, 20 gauge (AWG)
shielded cable with drain wire
(for up to 2000 feet, 600 meters).