3.2 Wiring the EX-5175-EC to a Control Unit

C

AUTION

:

Area must be declassified during installation.

Run conduit and 16

AWG

(1.5

MM

2

)

wires to the enclosure from the power supply and controller. If the

EX-5175-EC

is

installed in a hazardous location as defined by the National Electrical Code, then ALL wiring must be in accordance with the
National code and any local governing codes.

Open the enclosure, and remove the 2 screws that retain the display overlay to the circuit board.

Use caution when removing the over lay. Do not damage the magnetic switches.

Remove the two overlay standoffs and remove the circuit board, exposing the terminal strips on the bottom of the circuit board.
Do not disconnect the circuit board wiring.

Connect the wires from the controller (power supply) to the supplied J4 plug then attach to J4 terminal.

See Figure 3 for locations

J4

P

LUG

T

ERMINAL TO

C

ONTROLLER

W

IRING

Position

Function

1 +

24

V

DC

power

2

GND

3

4 - 20 mA out

4*

RS-485 D+

5*

RS-485 D–

*Contact

ENMET

for Modbus

Address information

Figure 3: Terminal Positions EX-5175-EC Sensor/Transmitter

When wiring is complete, reassemble the

EX-5175-EC

. Use caution when installing the overlay so as not to damage the

magnetic switches. Put the cover back on the S/T Do Not apply power to the S/T without the cover in place.

Circuit Board Bottom View

5
4
3
2
1

J 4

J 8

1 2 3

P l u g J 4

To J4

Wires to

Controller

Sensor/Transmitter Enclosure
Cutaway View

Printed Circuit Board

(PCB)

Display Overlay

Display Overlay Screws

(2 places)

Display Overlay Standoffs

(2 places)

Magnetic Switches

(2 places)

Magnetic Switches

(2 places)

Printed Circuit Board (PCB)

J4 and J8 Terminals are

located on the bottom
side of PCB

Display Overlay

Display