Aution, Arning – EXFO BV10 Performance Endpoint Unit User Manual
Page 20

Getting Started
14
BV10
Connecting the Power
3. Connect the other end of the wires to the DC power source.
4. To add a redundant DC power source on the BV10, repeat step 1
through step 3.
C
AUTION
The DC input feeds to the equipment must be protected by 20 A rated
maximum breaker provided as part of the building installation.
Permanently connected equipment must have a switch or
circuit-breaker for disconnection. If the switch is not part of the kit:
Include a switch or circuit-breaker in the installation.
The switch must be located easily, and placed near the equipment.
The switch must be specified as the disconnecting device for the
equipment.
W
ARNING
To avoid serious injuries as well as irreparable damages to your unit,
ALWAYS TURN OFF BOTH DISCONNECT DEVICES BEFORE OPENING OR
SERVICING THE UNIT.