Glow-worm Energy Saver 80 - 100 and Gave Valve User Manual

Page 39

Advertising
background image

LPG MODELS - ONLY

Please refer to the specific instruction relating to your

model and check/adjust the CO2 value, refer to table

overleaf.

Gas valve setting

All gas valves are tested and factory set during manufac-

ture.

It should not be necessary to adjust the gas valve.

NOTE: Safe combustion can only be verified by measuring

CO/CO2 ratio. This must not exceed the value shown in

the table overleaf.

● Shut down boiler.

● Connect a CO2 analyser to the combustion test point.

● Start the boiler.

● Repeatedly press the ‘mode’ button on the boiler fascia
until the symbol “

L

” appears. Press and hold the ‘mode’

button for greater than one second until the decimal point

is flashing on the display. The boiler is now locked at mini-

mum input, refer to the CO2 setting table and check that

the CO2 value is to specification, if adjustment is required,

proceed as follows.

NOTE: The adjustment should be made in 1/8 of a turn

increments, waiting 1 minute to allow the appliance to

stabilise.

● To adjust the CO2, remove protective cap (b) from the

gas valve. Carefully turn the gas valve adjuster until the

correct CO2 value is obtained according to table minimum

column.

● To check the combustion at full rate repeatedly press
the mode button on the boiler fascia until the symbol “

H

appears. Press and hold the mode button until the decimal

point on the display flashes.The boiler is now locked at

maximum input.

● Allow the boiler to run for a few minutes to stabilise and

check the CO2, refer to the CO2 setting table and check

that the CO2 value is to specification.

● Check the CO/CO2 combustion ratio does not exceed

the value in the table overleaf.

If the CO2 or CO/CO2 combustion ratio are not as

specified please refer to the “Completion” paragraph of

these instructions.

Check the Gas Inlet Pressure and Gas Rate

On completion, test the gas installation for tightness using

the pressure drop method and suitable leak detection fluid,

purge in accordance with the above standard.

NOTE: Due to the modulating operation of the boiler and

the need to check the gas inlet pressure and measure the

gas rate at maximum rate, it will be necessary to force it to

maximum.

Operational Gas Inlet Pressure

With ALL other gas appliances operating, check the

operational supply pressure at the gas service isolation

valve test point, refer to your Installation literature supplied

with your appliance.

The nominal supply pressure for Natural Gas (G20) is

20mbar.

Turn the taps and appliances off, then disconnect the

pressure gauge.

Additionally the safe nominal maximum heat input of the

appliance can be achieved at an inlet pressure down to

15mbar.

NOTE: The BURNER PRESSURE cannot be measured

and is not used to measure the gas rate.

Gas Rate

Make sure that ALL other gas burning appliances and pilot

lights are off.

NOTE: To check the combustion at full rate repeatedly

press the mode button on the boiler fascia until the sym-
bol “

H

” appears. Press and hold the mode button until

the decimal point on the display flashes.The boiler is now

locked at maximum input.

Allow the boiler to run for a few minutes to stabilise and

check the CO2.

Check the gas rate using the gas meter test dial and stop

watch, at least 10 minutes after the burner has lit, see

table below for approximate rates.

In communal or LPG installations where the gas rate

cannot be measured it is acceptable to measure the

combustion rate as described in the servicing section.

On completion, reset the boiler to normal operation by

referring to the Installation and Servicing Instructions.

Completion

If it is not possible to achieve the required results for

either the combustion or gas rates, it will be necessary to

complete a full service of the appliance and then repeat

the combustion check procedure. If after servicing and

adjustment of the appliance the combustion values are still

unacceptable and after further remedial work has been

carried out, the appliance must be disconnected until the

CO/CO2 ratio is acceptable. Advice can be sought from

the Saunier Duval Technical Helpline 017730828400.