2 water sytem – Glow-worm EnergySaver 60 User Manual

Page 10

Advertising
background image

10

221836B

Diagram 2.5

METHOD 1

METHOD 2

METHOD 3

SUPPLY STOP
VALVE

SUPPLY
PIPE

HOSE
UNIONS

SERVICING
VALVE

TEMPORARY
HOSE

HEATING
SYSTEM

HEATING
SYSTEM

TEMPORARY
HOSE

HOSE
UNIONS

SERVICING
VALVE

SUPPLY
PIPE

SUPPLY STOP
VALVE

DOUBLE CHECK
VALVE ASSEMBLY

HEATING
SYSTEM

SERVICING
VALVE

SUPPLY
STOP VALVE

SUPPLY
PIPE

HOSE
UNIONS

DOUBLE CHECK
VALVE ASSEMBLY

OVERFLOW

CISTERN

COMBINED
CHECK VALVE
AND VACUUM
BREAKER

PRESSURE
REDUCING
VALVE

0051M

2 Water Sytem

2.12 Pressure Gauge

A pressure gauge with a set pointer and covering at least 0 to
4bar (0 to 60lb/in

2

) shall be fitted permanently to the system is

a position where it can be seen when filling the system.

2.13 Domestic Hot Water Cylinder

SINGLE FEED INDIRECT CYLINDERS ARE NOT SUITABLE.

The hot water cylinder must be of the indirect coil type. It must
be suitable for working at a gauge pressure of 0.35bar above
the safety valve setting.

2.14 Water Makeup

Provision should be made for replacing water loss from the
system using a make up bottle or filling loop mounted in a
position higher than the top point of the system, connected
through a non-return valve to the return side of either the
heating circuit or the hot water cylinder.

Alternatively, provision for make up can be made using a filling
loop.

2.15 Filling a Sealed Water System

Provision for filling the system at low level must be made. Three
methods are shown in diagram 2.5. There must be no permanent
connection to the mains water supply, even through a non-
return valve.