Installation – Glow-worm Ultracom2 cxi User Manual

Page 16

Advertising
background image

0020085231_02 - 05/10 - Glow-worm

- 14 -

8 Hydraulic connection

8.1

Gas and water connections

The whole of the gas installation, including the meter, should

be inspected, tested for tightness and purged in accordance

with the current issue of BS6891 and in IE the current edition of

I.S.813 “Domestic Gas Installations”.

i

The appliance may contain a small amount of water,

place a water container beneath the boiler connections.

• Take care to clean the pipes before assembly removing any

debris or burrs. Grease and oils may need to be removed

they are not possible to remove by cleansing and flushing.

Foreign bodies in the system may enter the appliance and

interrupt its operation.

• Do not use any solvent products, due to the risk of damaging

the circuit.

a

Do not perform any 'hot work' directly under

the appliance, this may cause damage to the

appliance base. Heat may also damage the

isolation valves.

Always pre-assemble pipes before fitting them to

the boiler.

• Only use original seals supplied with the appliance.

• Check that there are no leaks. Repair if necessary.

1

2

3

4

5

6

7

6

Key

1 Heating return isolating valve + sealing washer ¾"

2 Cold water inlet isolating valve + sealing washer ¾"

3 Gas service isolating valve with pressure test point + sealing

washer ½"

4 Domestic hot water outlet isolating valve + sealing washer ¾"

5 Heating flow isolating valve + sealing washer ¾"

6 Connection Ø O.D. 22 mm

7 Connection Ø O.D. 15 mm

• Remove the protective caps from the boiler connections.

• Flush out the domestic hot water and the heating systems.

i

Before turning on the cold mains supply to the boiler

turn off the cold water inlet to the boiler, lock the filling

loop in the closed position and close its filling taps.

8.2

Safety Discharge Valve

B

A

3

4

2

1

Key

1 Compression fitting

2 PRV pipe

3 Pipe for PRV

4 Draining outlet

A PRV outlet - to outside

b Appliance drain tap

This must be extended, using not less than 15mm o.d. pipe,

to discharge, in a visible position, outside the building, facing

downwards, preferably over a drain.

To ease future servicing it is advisable to use a compression

type fitting to extend the safety discharge valve tube.

The pipe must have a continuous fall and be routed to a

position so that any discharge of water, possibly boiling,

or steam cannot create any danger to persons, damage to

property or external electrical components and wiring.

INSTALLATION