Installation – Glow-worm Ultracom2 cxi User Manual

Page 20

Advertising
background image

0020085231_02 - 05/10 - Glow-worm

- 18 -

Position Position of the flue terminal

mm

Horizontal flues
A

directly below an opening, air brick,

opening windows

300

B

above an opening, air brick, opening windows

300

C

horizontally to an opening, air brick, opening

windows

300

D

below gutter, drain/soil pipe

25

E

below eaves

25

F

below a balcony or car port

25

G

from vertical drain pipes and soil pipes

25

H

from internal/external corners

25

H*

to a boundary alongside the terminal

300

I

above adjacent ground or balcony level

300

J*

from surface or a boundary facing the terminal

600

Position Position of the flue terminal

mm

L

from opening (door/window) in car port

into dwelling

1200

M

vertical from a terminal

1500

N

horizontally from a terminal

300

Vertical flues
P

from another terminal

600

Q

above roof level

300

R

from adjacent opening window

1000

S

from adjacent wall to flue

300

(*) These dimensions comply with the building regulations,

but they may need to be increased to avoid wall staining and

nuisance from pluming depending on site conditions.

INSTALLATION

Advertising