TROUBLESHOOTING

TROUBLESHOOTING

The two most common causes of a malfunctioning gas appliance are:

1. Loose wiring connections

2. Construction debris clogging the pilot and/or gas control valve filter

OBSERVED PROBLEM

Ignitor will not spark or pilot will not light

Pilot will not stay lit

No gas to burner, although wall switch and
valve are set to the ON position

Frequent pilot outage

POSSIBLE CAUSE

1. No gas supply, or shutoff valve is OFF

2. Air in gas line

3. Construction debris clogging pilot orifice

4. Low gas pressure

5. Kinked pilot line

6. Control valve knob is not opening

7. No power to unit or the ignition module

or power transformer is bad

8. Vent damper not fully open

1. Loose wiring on ignitor wire to ignition

module and/or poor ground to ignition
module

2. Pilot flame too low to sense

1. Wall switch wires defective or too long
2. Thermopile not generating sufficient

voltage

1. Pilot flame may be too low, causing

safety pilot to “drop out”

2. Improper venting or excessive blockage

REMEDY

1. Check to see if you have gas supply and

that equipment shutoff valve is opened

2. Repeat lighting procedure several times

to purge all air out of lines. If after re-
peated attempts appliance does not light,
call for qualified service and repair.

3. Remove debris and dirt, inspect and

clean any other possible obstructions

4. Contact your gas supplier to check

pressure

5. Have a qualified technician replace pi-

lot line

6. Replace control valve (Refer to Replace-

ment Parts, page 18)

7. Check that main power is on and that all

wire connections are made correctly to
the ignition model (see Wiring Diagram,
page 18). Check for 24 VAC at the sec-
ondary side of the transformer. If 24
VAC is present, and the module does not
oporate, have the module replaced oth-
erwise have the transformer replaced.

8. Open vent damper until fully locked in

OPEN position

1. Check wiring connection. Refer to wir-

ing diagram (see Wiring Diagram, page
18) and/or check ground wire to igni-
tion module

2. Clean and adjust pilot burner and check

gas supply and inlet pressure to unit

Note:

Have a qualified technician replace

pilot assembly if broken or corroded

1. Check electrical connections
2. Recheck problems 1 and 2

1. Clean and adjust pilot flame for maximum

flame impingement on thermopile

2. Have the vent system inspected, includ-

ing the termination cap. Remove any
restriction or obstruction

Note:

For additional help, visit DESA’s technical service web

site at

www.desatech.com

.

Note:

Before troubleshooting the system, make sure the gas shutoff

valve is ON.