OPERATION

___________________________________________________________________

2-3

of the System 1100. The operator must be in the Main menu and have
the keyswitch in the PROG position to access this function.

Automatic setup stores the highest and lowest peak tonnage from
sixteen successive strokes. High setpoints are calculated as the
highest peak tonnage plus a user selected percentage of channel
rating (the auto setup tolerance), low setpoints are the lowest
peak tonnage minus the auto setup tolerance, and reverse setpoints
are the highest reverse reading plus the auto setup tolerance.
Automatic setup sets all setpoints, high, low, and reverse, for the
peak and for all data windows (if used).

When Automatic Setup is begun by the operator, the AUTO SETUP
indicator will turn on and the automatic setup screen will appear
as shown below.

While the keyswitch is in the PROG position, the automatic setup
tolerance will flash, indicating that it can be changed. The
tolerance can be adjusted up to 30% or down to 1% using the up and
down arrow keys respectively.

The number of STROKES NEEDED will count down as the operator cycles
the machine. When all sixteen strokes have been made the System
1100 will calculate and store all setpoints. The AUTO SETUP light
will then go out, and the Main menu will again appear. The
setpoints are stored in the current setup just as if they had been
entered manually.

The automatic setup procedure can be aborted at any time before the
sixteenth stroke by pressing the CLEAR key or the EXIT key. The
previously entered setpoints will then remain in effect.

WARNING! While in Automatic Setup Mode (when AUTO SETUP light is
on) the System 1100 is effectively BYPASSED. All high, low, and
reverse alarms are turned OFF. Only machine rating alarms are
active.

2.1.2.2 LOW LIMIT ON/OFF key

AUTO SETUP TOL: 5%
STROKES NEEDED: 16