Mounting for nema 2, Dual auxiliary switch (-s option), Scale. figure 12 – Dodge EN221 User Manual

Page 5: Mounting for nema 2 rating, Dodge engineering & controls, inc, Installation

Advertising
background image


Dodge Engineering & Controls, Inc.

Toll Free (877) 334-2875 Fax: (978) 244-1422

Installation

EN221 and EN310 Non-Spring Return Electronic Actuators

90

90

EA0676R1

PUSH

Figure 12.

4. Determine the angle of rotation for the damper

blade shaft. Subtract that amount from 90°.

5. Remove the shaft adapter and insert it with the

position indicator pointing to mark on the scale
calculated in the previous step. Figure 13.

90

90

EA0677R1

PUSH

ANGLE

OF

RO

TA

TIO

N

Figure 13.

6. Attach the clip.

7. Rotate the damper blade shaft to its "0" position.

8. Return the actuator to the damper shaft and

tighten the shaft adapter to the damper shaft.

Mounting for NEMA 2 Rating

<

90

<

90

90

NEMA 2

EA1152R1

Figure 14. Acceptable NEMA 2 Mounting Position

for Single and Tandem Applications.

Dual Auxiliary Switch (-S option)

A

-5

°

0

°

10

°

20

°

30

°

70

°

80

°

90

°

0

°

10

°

20

°

30

°

70

°

80

°

90

°

B

EA0413R2

Figure 15.

Actuator rotary range with the shaft adapter mounted at
position 0.

Setting range for Switches A and B: 0 - 90°

Setting interval: 5°

Switching hysteresis: 2°

UL Doc. No. 129-272

EAI/EN-5

Dodge Engineering & Controls, Inc.

Rev. 5, Jan., 2005

Advertising