Zero span control signal adjustment (-zs option), Dodge engineering & controls, inc, Installation – Dodge EN221 User Manual

Page 6

Advertising
background image


Dodge Engineering & Controls, Inc.

Toll Free (877) 334-2875 Fax: (978) 244-1422

Installation

EN221 and EN310 Non-Spring Return Electronic Actuators

Factory setting:

Switch A 5°
Switch B 85°

To change the settings of A and B:

• Make sure the actuator is in the 0 position. The

scale is valid only in the 0 position.

• Use a flat-blade screwdriver to turn the switch

adjustment dials to the desired setting at which a
signal is to be given.

80

70

60

50

B

90

AUX

SWITCH

ADJ

20

30

40

10

20

40

A

70

EA0304R1

Figure 16. Dual Auxiliary Switch Dials.

Zero Span Control Signal Adjustment (-ZS option)


The offset (start point) and
span of the control signal
can be adjusted. The offset,
U0, (start point) can be
adjusted between 0 to
5 VDC. The span, ∆U, can
be adjusted between 2 to
30 VDC.

100

0

U

O

U (max. 30 V)

Y

U

(v)

Y

S

(%)

EA041

1R1

2

5

10

35

2)

1)

3)

Ys

Mechanical positioning range

(100% = angle of rotation 90°)

Yu Control

signal

U0

Offset (start point)

∆U Span


Examples above:

Ex. 1. U0 = 0V, ∆U = 2V

The minimum working
range for Ys = 100%.

Ex. 2. U0 = 5V, ∆U = 30V

The maximum working
range for Ys = 100%

Ex. 3. U0 = 0V, ∆U = 10V

Factory setting

Offset, Uo

2

4

0

1

3

5

Span, U

30

2

15

10

5

20

25

Control
Signals

Uo

U

EA0287R1

Figure 17. The Minimum, Factory Setting, and Maximum

Control Signal Adjustment.

Figure 18. Setting for

10V Span, 0 Offset.

Example:

Open the actuator from 0% to 50% (45°) using a control signal of Umin = 2V to Umax = 10V.
Calculating the value of ∆U:

V

16

50

2)

(10

x

100

%

in

rotation

of

angle

Working

min)

U

max

(U

%]

[

100

U

=

=

=

UL Doc. No. 129-272

EAI/EN-6

Dodge Engineering & Controls, Inc.

Rev. 5, Jan., 2005