Chapter 3: Configuring the Module

3-9

User’s Manual Pub. 0300274-01 Rev. A.0

-

Attribute. Enter the PLC variable attribute.

-

Object Name. Enter the BACnet object name. Use a
meaningful description, such as Damper Angle.

-

Object Type. Click on the field and select the relevant
object type for the PLC tag:

-

Object ID. This is the BACnet object instance. Valid
range is from 0 to 63, which means you can define 64
object instances of each object type. Each object is
uniquely defined by object-instance and type. Support is
provided for 256 BACnet objects. Click on the field and
type in the ID value.

-

Present Value. Not editable (from user interface). When
the BACnet module requests the PLC report a specific
value, the PLC returns the present value in the specific
index. Example: When the PLC receives a BACnet
command to report the present value of Analog Value
Index 1, the PLC sends the present value of AV 1 back
to the requester. This value is displayed in the Present
Value
column.

Delete Tags. To delete a tag, click the Delete Tag button:

The selected tag row is deleted.

Reload Tags. Reloads tag preset values.

Save Tags. Saves tag changes. You have to save changes before
you may generate structured text from the tag information.

Edit XML. Allows you to manually edit tag information in
XML format. See Editing XML Tag Information next.

Generate Structured Text. Converts tag information to CCW
structured text. See Generating Structured Text later in this
chapter.