The first step is to create Local Variables for the Main program.

The second step is to paste in the structured text generated by the Module
configuration user interface to the Main program of the CCW. Below is an
example of this Main program.

A variable called

tag1

is converted to ULINT variable

bacnet_convert_var

and then placed at offset 0 of the byte array table because you are writing
AnalogInput 0. If it is AnalogInput 1, the offset will be 8 as each BACNET
object instance takes 8 bytes. Variable

bacnet_convert_mode

is 1. This means

this is a write operation. 0 identifies a read operation:

(* 0, AnalogInput, aiaaa *)

bacnet_convert_var := ANY_TO_ULINT(tag1);
bacnet_convert_offset := 0;
bacnet_convert_mode := 1;
bacnet_convert_fn(bacnet_convert_offset,
bacnet_convert_var, bacnet_convert_mode);

(* Write Input Table to Module *)

bacnet_module_address := 112;
bacnet_module_datalen := 8;
bacnet_module_write_fn(TRUE, BACNET_MODULE_SLOT,
bacnet_module_address, bacnet_module_datalen,
bacnet_convert_fn.bac_raw_tbl);