Specifications

Parameter

Specification

Load Rating

EV-12015

15 Amps at 120 Volts

EV-12020

20 Amps at 120 Volts

EV-20815

15 Amps at 120/230 Volts Split Phase

EV-20820

20 Amps at 120/230 Volts Split Phase

EV-23010

13 Amps at 230V Single Phase

Voltage Protection
Rating (VPR)

EV-12015
EV-12020

330V All Modes

EV-20815
EV-20820

700V All Modes

EV-23010

NA

Attenuation

Normal
Mode

EV-12015
EV-12020
EV-20815
EV-20820
EV-23010

> 30 dB 80kHz

– 50MHz

Common

Mode

EV-12015
EV-12020

> 30 dB 70kHz

– 50MHz

EV-20815
EV-20820
EV-23010

> 30 dB 200 kHz

– 50MHz

Power Requirement

(no load)

EV-12015
EV-12020
EV-20815
EV-20820
EV-23010

4 Watts

Under-Voltage
Shutdown

120V Models

Adjustable from 0 V to 110 V. Default 80 V.

208/230V Models

Adjustable from 0 V to 220 V. Default 160 V.

Under-Voltage
Record

120V Models

Adjustable from 0 V to 110 V. Default 100 V.

208/230V Models

Adjustable from 0 V to 220 V. Default 180 V.

Under-Voltage
Restore

120V Models

Adjustable from 80 V to 110 V. Default 105V.

208/230V Models

Adjustable from 160 V to 220 V. Default 190 V.

Over-Voltage
Shutdown

120V Models

Adjustable from 130 V to 160 V. Default 150 V.

208/230V Models

Adjustable from 260 V to 300 V. Default 280 V.

Over-Voltage
Record

120V Models

Adjustable from 130 V to 160 V. Default 145 V.

208/230V Models

Adjustable from 260 V to 300 V. Default 270 V.

Over-Voltage
Restore

120V Models

Adjustable from 130 V to 160 V. Default 140 V.

208/230V Models

Adjustable from 260 V to 300 V. Default 260 V.

Internal Memory Capacity

512 Power Quality Events with Timestamp
138 Day Electrical Parameter History at 30 minute intervals

Timestamp Accuracy

± 1% Typical Product Accuracy

Measurement
Accuracy

120V Models

± 2% Typical product accuracy

208/230V Models

± 2% Typical product accuracy

Response Time

Over-Voltage

90 ms

Under-Voltage

200 ms

Power Outage Event Definition

AC Voltage has dropped below 20V


** Specifications subject to change without notice
** All listed specifications obtained at an ambient temperature of 25°C