Technical data – relay version – TFC Group Feeling RF Room Thermostat User Manual

Page 5

Advertising
background image

GB

45

Technical data – Relay version

Power supply:

2 x 1.5 V AA LR6 alkaline batteries

Battery service life:

2 years (depending on switching frequency)

Switching output:

SPDT (potential-free)

Switching capacity:

8 (3) A 250 V AC

Wire cross-section to relay terminals: 0.5 mm

2

– 1.5 mm

2

Room temperature display resolution: 0.1ºC

Temperature setting display:

Program:

+5ºC…+32ºC (0.5ºC steps)

Frost protection: 5ºC (adjustable 3ºC…7ºC)

Time setting resolution:

Time of day:

1 minute

Program:

30 minutes

Temperature measurement

(heating system):

3 K/hour

Programming:

weekly program with up to 48 time and temperature programs

changes

Pre-programmed programs:

4 + 1 user-defined

Protection class/type:

II/IP40

Operating temperature range:

Max. 45ºC

Operating humidity range:

10% to 90% RH non-condensing

Dimensions H x W x D (mm):

87 x 154 x 27