Duct system, Water piping, Condensate drain – WaterFurnace Envision2 User Manual

Page 12: Duct system water piping

Advertising
background image

12

ENVISION

2

COMPACT INSTALLATION MANUAL

An air outlet collar is provided on vertical top flow units

and all horizontal units to facilitate a duct connection.

A flexible connector is recommended for discharge

and return air duct connections on metal duct systems.

Uninsulated duct should be insulated with a minimum of

1-inch duct insulation. Application of the unit to uninsulated

ductwork in an unconditioned space is not recommended

as the unit’s performance will be adversely affected.

If the unit is connected to existing ductwork, check the duct

system to ensure that it has the capacity to accommodate

the air required for the unit application. If the duct is too

small, as in the replacement of heating only systems, larger

ductwork should be installed. All existing ductwork should

be checked for leaks and repaired if necessary.

Duct System

Water Piping

The duct system should be sized to handle the design

airflow quietly and efficiently. To maximize sound

attenuation of the unit blower, the supply and return

plenums should include an internal duct liner of fiberglass

or constructed of ductboard for the first few feet. On

systems employing a sheet metal duct system, canvas

connectors should be used between the unit and the

ductwork. If air noise or excessive airflow is a problem, the

blower speed can be changed.

The proper water flow must be provided to each unit

whenever the unit operates. To assure proper flow, use

pressure/temperature ports to determine the flow rate.

These ports should be located at the supply and return

water connections on the unit. The proper flow rate cannot

be accurately set without measuring the water pressure

drop through the refrigerant-to-water heat exchanger.

All source water connections on commercial units are

fittings that accept a male pipe thread (MPT). Insert the

connectors by hand, then tighten the fitting with a wrench

to provide a leakproof joint. When connecting to an open

loop (groundwater) system, thread any copper MPT fitting

into the connector and tighten in the same manner as

described above.

1/2'' Pitch

Drain

1.5 in.

1.5 in.

PVC tube stub

PVC coupling

Vent (if needed)

PVC tube stub

1/8 in. per foot

Unit Pitch for Drain

Horizontal Drain Connection (Composite Drain Pan)

Condensate Drain

On vertical units, the internal condensate drain assembly

consists of a drain tube which is connected to the drain

pan, a 3/4 in. PVC female adapter and a flexible connecting

hose. The female adapter may exit either the front or the

side of the cabinet. The adapter should be glued to the

field-installed PVC condensate piping. On vertical units, a

condensate hose is inside all cabinets as a trapping loop;

therefore, an external trap is not necessary.

On horizontal units, a PVC stub or stainless steel tube

is provided for condensate drain piping connection. An

external trap is required (see below). If a vent is necessary,

an open stand pipe may be applied to a tee in the field-

installed condensate piping.

Advertising