Reference calculations, Legend, Refrigerant circuit guideline – WaterFurnace Envision2 User Manual

Page 46

Advertising
background image

46

ENVISION

2

COMPACT INSTALLATION MANUAL

Symptom

Head

Pressure

Suction

Pressure

Compressor

Amp Draw

Superheat

Subcooling

Air Temp.

Differential

Water Temp.

Differential

Under Charged System (Possible Leak)

Low

Low

Low

High

Low

Low

Low

Over Charged System

High

High

High

Normal

High

Normal/Low

Normal

Low Air Flow Heating

High

High

High

High/Normal

Low

High

Low

Low Air Flow Cooling

Low

Low

Low

Low/Normal

High

High

Low

Low Water Flow Heating

Low/Normal

Low/Normal

Low

Low

High

Low

High

Low Water Flow Cooling

High

High

High

High

Low

Low

High

High Air Flow Heating

Low

Low

Low

Low

High

Low

Low

High Air Flow Cooling

Low

High

Normal

High

Low

Low

Normal

High Water Flow Heating

Normal

Low

Normal

High

Normal

Normal

Low

High Water Flow Cooling

Low

Low

Low

Low

High

Normal

Low

Low Indoor Air Temperature Heating

Low

Low

Low

Normal

High

Normal

Normal/High

Low Indoor Air Temperature Cooling

Low

Low

Low

Normal/Low

High

Low

Low

High Indoor Air Temperature Heating

High

High

High

Normal/High

Normal/Low

Low

Normal

High Indoor Air Temperature Cooling

High

High

High

High

Low

Low

High

Restricted TXV (Check Service Advisory)

High

Low

Normal/Low

High

High

Low

Low

Insufficient Compressor (Possible Bad Valves)

Low

High

Low

High

Normal/High

Low

Low

TXV - Bulb Loss of Charge

Low

Low

Low

High

High

Low

Low

Scaled Coaxial Heat Exchanger Heating

Low

Low

Low

Normal/Low

High

Low

Low

Scaled Coaxial Heat Exchanger Cooling

High

High

High

Normal/Low

Low

Low

Low

Restricted Filter Drier

Check temperature difference (delta T) across filter drier.

7/6/10

Refrigerant Circuit Guideline

Reference Calculations

Heating Calculations:

Cooling Calculations:

LWT = EWT +

LAT(DB) = EAT(DB) -

LC = TC - SC

S/T =

HR

gpm x 500

SC

cfm x 1.08

SC

TC

HE

gpm x 500

LWT = EWT -

LAT = EAT +

TH = HC + HWC

HC

cfm x 1.08

Legend

ABBREVIATIONS AND DEFINITIONS:

cfm

= airflow, cubic feet/minute

EWT = entering water temperature, Fahrenheit
gpm = water flow in gallons/minute
WPD = water pressure drop, PSI and feet of water
EAT

= entering air temperature, Fahrenheit

(dry bulb/wet bulb)

HC

= air heating capacity, MBtu/h

TC

= total cooling capacity, MBtu/h

SC

= sensible cooling capacity, MBtu/h

KW

= total power unit input, kilowatts

HR

= total heat of rejection, MBtu/h

HE

= total heat of extraction, MBtu/h

HWC = hot water generator capacity, MBtu/h
EER

= Energy Efficient Ratio

= BTU output/Watt input

COP = Coefficient of Performance

= BTU output/BTU input

LWT = leaving water temperature, °F
LAT

= leaving air temperature, °F

TH

= total heating capacity, MBtu/h

LC

= latent cooling capacity, MBtu/h

S/T

= sensible to total cooling ratio