Envision console controls cont, Optional fx10 microprocessor and bas interface – WaterFurnace Envisio Series Console User Manual

Page 31

Advertising
background image

31

ENVISION CONSOLE INSTALLATION MANUAL

Control Timing & Fault Recognition Delays

Lead compressor “ON” delay ..........................................90 seconds

(not applicable for single compressor models)

Minimum compressor “ON” time ...................................... 2 minutes

(except for fault condition)

Short cycle delay ..................................................................... 5 minutes

Random start delay .......................................................0-120 seconds

High pressure fault ................................................................. <1 second

Low pressure fault ...............................................................30 seconds

Freeze detection fault ...........................................................30 seconds

Condensate overflow fault ...............................................30 seconds

Low pressure fault bypass ................................................... 2 minutes

Freeze detection fault bypass ............................................ 2 minutes

Optional FX10 Microprocessor
and BAS Interface

The FX10 is a microprocessor based control that not

only monitors and controls the heat pump but also can

communicate any of this information back to the building

automation system (BAS). This means that not only does

the control monitor the heat pump at the unit you can also

monitor and control many the features over the BAS. This

clearly puts the FX10 in a class of its own.

The control will enumerate all fault conditions (HP, LP, CO,

LOC, and Freeze Detection) over a BAS as well as display

them on a medium user interface (MUI). HP, LP, CO and

Freeze Detection faults can all be reset over a BAS. A

Loss Of Charge fault can not be reset or bypassed until

the problem has been corrected. A MUI is invaluable as a

service tool for the building service team.

The unit can be commanded to run by a typical heat

pump thermostat or run based on heating and cooling

set points supplied by a BAS. The control board is wired

with quick connect harnesses for easy field change out

of a bad control board. All ECM2.3 variable blower speed

settings can be changed over a BAS or with a MUI. The

control has an input programmed to enable field installed

emergency heat in the event that the compressor is locked

out. This input can also be commanded on from a BAS

as needed. An alarm history can be viewed through the

MUI and will be held in memory until the unit is power

cycled. Relative humidity can be read by a 0-5VDC

humidity sensor that is displayed over the network. If you

are using an ECM2.3 blower motor the control can enable

dehumidification mode based on a set point in the control.

The dehumidification set point itself can also be changed

over a BAS or with a MUI. Dehumidification mode can also

be enabled by the BAS. Because the FX10 is not factory

configured to read CO

2

levels, contact the factory for

application assistance.

The FX10 control has unused analog and digital inputs

for field installed items such as air temperature, water

temperature, CO

2

or current status switches. The control has

unused binary and PWM outputs that can be commanded

over the BAS for field use. An optional Medium User

Interface (MUI) for control setup and advanced diagnostics

is available with some mounting kits, MUIK1 - Panel mount

version and the MUIK2-Wall mount version.

Zone Sensors

There are two options for zone sensors that can be used

with the FX10 control. Both sensors use a Johnson controls

A99 positive temperature coefficient type sensor. The

TAXXJ02 has a set point adjustment now which will give

the end user a +/- 5°F adjustment from the set point as

well as a push button that can be used for temporary

occupancy. The control leaves the factory set to operate

with a TAXXJ02 sensor and can be changed to read the

TAXXA01 sensor through a building automation system or

with a user interface.

Standard Features

• Anti Short Cycle

• High Pressure Protection

• Low Pressure Protection

• Freeze

Detection

• Loss Of Charge Detection

• Random

Start

• Display for diagnostics

• Reset Lockout at disconnect or through BAS

• 2 Accessory outputs

• Optional BAS add-on controls

DDC Operation and Connection

Other optional network protocol boards that can be added

to the FX10 are:

• Johnson Control N2

• LonWorks

• BACnet

- MS/TP @ 19,200 Baud rate

- Limit devices to 30 on a single trunk line.

Envision Console Controls cont.