Envision console controls cont – WaterFurnace Envisio Series Console User Manual

Page 33

Advertising
background image

33

ENVISION CONSOLE INSTALLATION MANUAL

mode. The delay should not be less than 1 second and not

longer than 120 seconds. If the control is in test mode the

random start delay will be shortened to 5 seconds.

Compressor Fixed On Delay Time

The Compressor Fixed On Delay Time will ensure that the

compressor output (B02) is not enabled for (90) seconds

after the control receives a call to start the compressor.

This delay is adjustable from 30 – 300 seconds over a BAS

or a MUI. If the control is in test mode the Compressor

Fixed On Delay Timer will be shortened to 5 seconds.

Compressor Minimum On Delay

The compressor minimum on delay will ensure that the

compressor output is enabled for a minimum of (2)

minute each time the compressor output is enabled. This

will apply in every instance except in the event the high

pressure switch is tripped or emergency shutdown then

the compressor output will be disable immediately.

Compressor Short Cycle Delay Time

The compressor short cycle time delay will ensure that

the compressor output will not be enabled for a minimum

of (5) minutes after it is disabled. This allows for the

system refrigerant pressures to equalize after the

compressor is disabled.

Heating Cycle

On a call for heating, the blower enable output and

accessory output 2 will turn on immediately after the

random start delay timer has been satisfied. If the

compressor short cycle time delay has been satisfied,

the compressor will turn on after the blower enable and

accessory output 2 are on and the fixed compressor start

delay timers have been satisfied.

Auxiliary heat output can be controlled over the BAS.

Set Point Control Mode

In set point control mode the reversing valve output

will be disabled. As the temperature drops below the

heating set point and begins to operate in the heating

proportional band, the low capacity compressor

output (BO-2) will be enabled. A PI loop in the

programming of the control will determine when

the full capacity compressor output (BO-4) is to be

enabled. The compressor must be operating in low

capacity for a minimum of 30 seconds before the full

capacity compressor output can be enabled.

Thermostat Control Mode

In thermostat mode the compressor will be cycled

based on Y1 calls from a room thermostat. When

the control receives a Y1 command (BI-7) from the

thermostat, the compressor output (BO2) will be

enabled. During the heating cycle the reversing valve

will be commanded into the off position.

Cooling Cycle

On a call for cooling, the blower enable output and

accessory output 2 will turn on immediately after the

random start delay timer has been satisfied. If the

compressor short cycle time delay has been satisfied,

the compressor will turn on after the blower enable and

accessory output 2 are on and the fixed compressor start

delay timers have been satisfied.

Set Point Control Mode

In set point control mode the reversing valve output

will be enabled. As the temperature falls below the

cooling set point and begins to operate in the cooling

proportional band, the low capacity compressor

output (BO-2) will be enabled. A PI loop in the

programming of the control will determine when

the full capacity compressor output (BO-4) is to be

enabled. The compressor must be operating in low

capacity for a minimum of 30 seconds before the full

capacity compressor output can be enabled.

Thermostat Control Mode

In thermostat mode the compressor will be cycled

based on Y1 calls from a room thermostat. When

the control receives a Y1 command (BI-7) from the

thermostat, the compressor output (BO2) will be

enabled. During the cooling cycle the reversing valve

will be commanded into the “ON” position.

Emergency Heat/Network Enabled Output (BO5)

This output is set from the factory to enable/disable

emergency heat. If a problem occurs with the unit resulting

in the compressor being locked out in heating mode,

the control will automatically enable this output to turn

on field installed electric heat. This output is interlocked

with the blower proving input BI-6 (Blower proving

sensors must be field supplied and installed). BI-6 must

be connected to PB2 position 3 (see unit schematic) in

the field if no blower proving sensor is desired. There is a

configurable parameter available through a BAS network

that must be enabled if this output is to be commanded

over the BAS network.

MUI Alarm History Reporting

If a fault occurs the fault will be recorded in history for

display on the medium user interface in the History Menu.

Each fault type will be displayed in the history menu with

a number between 0 and 3. A reading of 3+ will mean

that fault has occurred more than three times in the past.

The history menu can be cleared with a power cycle only.

Alarm date and time are not included in the history.

Envision Console Controls cont.