Hydronic section – WaterFurnace Envision Hydronic User Manual

Page 13

Advertising
background image

13

NSKW INSTALLATION MANUAL

Hydronic Section

General guidelines are shown below for component
selection and design/installation criteria for the piping
system. Local codes supersede any recommendations in

this manual.

Shut Off/Flow Regulation Valves

Use full port ball valves or gate valves for component
isolation. If valves are going to be used frequently, ball
valves are recommended. Globe valves are designed for
flow regulation. Always install globe valves in the correct
direction (fluid should enter through the lower body
chamber).

Check valves

Swing check valves must be installed in the horizontal

position with the bonnet of the valve upright. Spring check

valves can be mounted in any position. A flow check valve

is required to prevent thermo-siphoning (or gravity flow)
when the circulator pump is off or when there are two

circulators on the same system.

Storage (Buffer) Tank

A buffer tank is required for all hydronic heating systems

using Envision NSKW heat pumps. The tank should be sized
to provide 2 gallons [7.6 L] of storage capacity for every

300W of nominal heat pump capacity.

Pressure Relief Valve

Most codes require the use of a pressure relief valve if a
closed loop heat source can be isolated by valves. Even
if local code does not require this device, WaterFurnace
recommends its installation. If the pressure relief valve in
the buffer tank is not already rated at 207 kPa maximum
pressure, one must be installed. The pressure relief valve
should be tested at start up for operation. Note that the
waste pipe must be at least the same diameter as the valve
outlet (never reduce), and valves may not be added to this
pipe. The bottom of the pipe must terminate at least 15 cm
above the floor. If the piping is connected to a drain, there
must be an air gap.

Backflow Prevention Check Valves

Most codes require backflow prevention check valves.
Note that a single check valve is not equal to a backflow
prevention check valve. Even if local code does not require
this device, WaterFurnace recommends its installation. This
is particularly important if the system will use antifreeze.

Pressure Reducing Valves or Feed Water Valves

This valve lowers the pressure from the make-up water line

to the system. Most are adjustable and directional. A “fast
fill” valve is required for initial filling of the system. Some
have screens, which must be cleaned after the initial filling.
If there is a restriction in the screen, the system could go to
0 kPa, potentially causing pumps(s) failure. A valve should
be installed on each side of the pressure reducing valve for
servicing. Both valves should have tags reading “Do not
shut this valve under normal operation – service valve only.”

Expansion Tanks

Expansion tanks are required on hydronic systems to help
absorb the pressure swings as the temperature in the
system fluctuates.

Elbows/Tees

Long radius elbows or two 45° elbows will lower pressure
drop. Standard tees have a greater restriction on the “T”
portion than tees designed with angled outlet ports.

Antifreeze

Antifreeze is required if any of the piping system is located

in areas subject to freezing.

Dielectric Unions

Dielectric unions are recommended whenever connecting
two dissimilar metals to one and other to prevent electro-

galvanic corrosion.

When using the various types of hydronic heat distribution

systems, the temperature limits of the geothermal system

must be a major consideration. In new construction, the
distribution system can easily be designed with the
temperature limits in mind. In retrofits, care must be
taken to address the operating temperature limits of the
existing distribution system. The maximum storage tank
temperature for the Envision NSKW is 54.4°C. Typical in
floor radiant systems require much lower temperatures,
typically 37.8°-46.1°C, which is ideal for the Envision NSKW.

Advertising