Fault diagnostics, Connection test, Length measurement – Pilz PSS SB TESTER D User Manual

Page 43

Advertising
background image

Operating Manual: PSS SB TESTER

7-1

Fault Diagnostics

If you detect faults on SafetyBUS p, the following tables may help you to
find the source of the fault and to rectify it.

Connection test

Problem

Resistance between
CAN_H and CAN_L
< 50

Resistance between
CAN_H and CAN_L
> 85

Short circuit detected

Cause

A terminating resistor has an
invalid value or there are too
many terminating resistors
present

A terminating resistor is
missing or has an invalid value

Short circuit

Correcting the problem

Check the terminating
resistors, both terminating
resistors must have a value of
120

Check the terminating
resistors, both terminating
resistors must have a value of
120

Check the wiring

Problem

Error message
“Measurement not OK” is
displayed

Cause

Length of bus line < 25 m

Correcting the problem

Cable runs < 25 m cannot be
measured

Length measurement