7-2

Operating Manual: PSS SB TESTER

Fault Diagnostics

Problem

Device’s signal level lies
outside the measurable
range

Error message “Problem
CAN_L” is displayed

Error message
“Measurement not OK” is
displayed

Device’s transmission
rate is incorrect

Error message "Network
config"

Cause

Connection is faulty or device
is defective

Short circuit between CAN_L
and earth

Connection between PSS SB
TESTER and SafetyBUS p is
interrupted or SafetyBUS p is
inactive

Device is defective

The transmission rate set on
the PSS SB TESTER may not
match the actual transmission
rate on SafetyBUS p

Correcting the problem

Check the connection. If
nothing helps, change the
device

Check line from CAN_L

Check whether SafetyBUS p
is active (SafetyBUS p status
LED on the PSS and devices
must be lit), check the
connection

Change the device

Check the transmission rate
setting

Signal test

Real-time mode

Problem

Failure rate (fr/s) > 0

Cause

The transmission rate set on
the PSS SB TESTER may not
match the actual transmission
rate on SafetyBUS p

Correcting the problem

Check the transmission rate
setting