WARNING: If the area in which the heater may be

operated is smaller than that defined as an uncon-
fined space or if the building is of unusually tight
construction, provide adequate combustion and ven-
tilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Sec-
tion 5.3 or applicable local codes.

AIR FOR COMBUSTION AND
VENTILATION

Continued

40,000

10,000

50,000

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_____________ Btu/Hr

Gas water heater*

_____________ Btu/Hr

Gas furnace

_____________ Btu/Hr

Vented gas heater

_____________ Btu/Hr

Gas fireplace logs

_____________ Btu/Hr

Other gas appliances* + _____________ Btu/Hr

Total = _____________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws com-
bustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

_____________ Btu/Hr

Vent-free heater

+ _____________ Btu/Hr

Total

= _____________ Btu/Hr

4.

Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

50,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. You must
provide additional fresh air. Your options are as follows:

A.

Rework worksheet, adding the space of an adjoining room. If the ex-
tra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See Ventilation Air From
Inside Building
.

B.

Vent room directly to the outdoors. See Ventilation Air From
Outdoors
.

C.

Install a lower Btu/Hr heater, if lower Btu/Hr size makes room un-
confined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can
support, the space is an unconfined space. You will need no additional fresh
air ventilation.

AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow For Heater Location (Cont.)

Ventilation Air

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space.
When ventilating to an adjoining unconfined space, you must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also remove door into
adjoining room (see option 3, Figure 2). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion
and Ventilation
for required size of ventilation grills or ducts.

Or

Remove

Door into
Adjoining

Room,

Option 3

Ventilation Grills

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room,

Option 1

Figure 2 - Ventilation Air from Inside Building

Figure 3 - Ventilation Air from Outdoors

Outlet
Air

Ventilated
Attic

Outlet
Air

Inlet
Air

Inlet Air

Ventilated

Crawl Space

To

Crawl

Space

To Attic

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Section 5.3, Air for Combustion and Ventilation
for
required size of ventilation grills or ducts.

IMPORTANT:

Do not provide openings for inlet or outlet air into

attic if attic has a thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.