Installation, Maintenance – ABUS Technologies MPT Melt Pressure Transmitter User Manual

Page 7

Advertising
background image

ABUS TECHNOLOGIES INC.

7

MPT

6. INSTALLATION


Recommendation

Before starting the machine, wait until the melt medium at the diaphragm of the PT

has reached its operating/processing temperature. If the machine is started before the

medium reaches its operating temperature, the PT will be damaged. If it is hard to tell when

the operating temperature has been reached, use a combined PT with thermocouple.

Operating temperature at the PT diaphragm is max. 400°C (752°F) for mercury filled

transmitters. Operating temperature at the PT diaphragm is max. 325°C (617°F) for food

grade oil filled transmitters.

Operating temperature at the PT diaphragm is maximum 518°C (1000°F) for filled

transmitters. Temperatures higher than the maximum recommended temperatures will

damage the PT. Ambient temperature for the electronics housing is maximum +85°C.

Higher range temperatures can result in damage and malfunction.

Do not install the pressure transmitter in places where this temperature is exceeded.

7. MAINTENANCE

Troubleshooting

FAULT

POSSIBLE CAUSE

RESOLUTION

No signal

Cable breakage or poor

contact

Check cable and contact, or replace.

No supply voltage

Check supply voltage.

String zero shift

when screwing in

Mounting hole

incorrectly produced

Check hole with test bolt, review with tool if

necessary.

Mounting torque too

high

Adjustment to recommended mounting torque.

No signal change

despite pressure

rise

Plug forming in front of

diaphragm

Check mounting hole; remove solidified plastic.

Diaphragm damaged

Send pressure transmitter to ABUS for repair.