Installation, Continued, Mantel clearances – Desa VML27NR User Manual

Page 8: Determining minimum mantel clearance, Minimum noncombustible material clearances

Advertising
background image

111115-01D

8

For more information, visit www.desatech.com

For more information, visit www.desatech.com

MANTEL CLEARANCES

In addition to meeting noncombustible material clearances, you
must also meet required clearances between fireplace openings and
mantel shelf on each side of the fireplace. If you do not meet the
clearances listed below, you will need a hood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel shelf and top of
fireplace opening, a hood is not required (see Figure 6).

Determining Minimum Mantel Clearance When
using a Hood

If minimum clearances in Figure 6 are not met, you must have a
hood. When using a hood there are still certain minimum mantel
clearances required. Follow minimum clearances shown in Figure
7, page 9 when using hood.

NOTICE: If your installation does not meet the mini-
mum clearances shown, you must do one of the
following:
• operate the logs only with the flue damper open
• raise the mantel to an acceptable height
• remove the mantel

Figure 6 - Minimum Mantel Clearances Without Using Hood

Minimum Non-
Combustible
Material

Minimum Non-
Combustible
Material Height

Distances to
Underside of
Mantel

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf

12"

(A)

18"

20"

22"

24"

All minimum
distances are
in inches

2

1

/2

"

6"

8"

10"

NOTICE: Surface temperatures of adjacent walls and
mantels become hot during operation. Walls and
mantels above the firebox may become hot to the
touch. If installed properly, these temperatures meet
the requirement of the national product standard.
Follow all minimum clearances shown in this manual.

INSTALLATION

Continued

Minimum Noncombustible Material Clearances

If Not Using Mantel

Note:

If using a mantel, proceed to If Using Mantel. If not using a

mantel, follow the information below.

You must have noncombustible material(s) above both fireplace
openings. Noncombustible materials (such as slate, marble, tile,
etc.) must be at least 1/2 inch thick. With sheet metal, you must have
noncombustible material behind it. Noncombustible material must
extend at least 8" up (for all models). If noncombustible material is
less than 12", you must install the fireplace hood accessory. See
Figure 5 at right for minimum clearances.

IMPORTANT:

If you cannot meet these minimum clearances, you

must operate heater with chimney flue damper open. Go to Install-
ing Damper Clamp Accessory for Vented Operation
, page 9.

If Using Mantel

You must have noncombustible material(s) above the fireplace
opening. Noncombustible materials (such as slate, marble, tile, etc.)
must be at least 1/2 inch thick. With sheet metal, you must have
noncombustible material behind it. Noncombustible material must
extend at least 8 inches up (for all models). If noncombustible material
is less than 12", you must install the fireplace hood accessory. Even
if noncombustible material is more than 12", you may need the hood
accessory to deflect heat away from your mantel shelf. See Figure 5
and 6 and Figure 7, page 9, for minimum clearances.

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.)
Above Fireplace

Heat Resistant
Material

(A)

Noncombustible

Requirements for

Material Distance (A) Safe Installation

12" or more

Noncombustible material OK.

Between 8" and 12"

Install fireplace hood accessory
(GA6050, GA6052 or GA6053, see
Accessories, page 27).

Less than 8"

Noncombustible material must be
extended to at least 8". See

Between

8" and 12", above. If you cannot
extend material, you must operate
heater with flue damper open.

INSTALLATION

Installation and Clearances (Cont.)
Mantel Clearances

Advertising