CIRCUTOR TCP1RS+ User Manual
CIRCUTOR Measuring instruments
TCP1RS+
M98253301-03-14A
TCP1RS+
 
The TCP1RS+ is a communications gateway that 
converts the Ethernet physical environment to RS-
485 serial communications. 
 
This document provides the instructions for use and describes
the operation of the TCP1RS + device. If misplaced, the
manual may be downloaded from the CIRCUTOR web site:
www.circutor.com
Disconnect the device from the power 
supply source before undertaking any 
maintenance, modification of connections, 
repairs, etc. If you suspect an operational 
fault in the unit or in its protection system, remove the 
unit from service. The design of the unit makes it easy 
to replace in the event of a fault. 
1.- DESCRIPTION
The TCP1RS+ device is a serial physical 
environment to Ethernet communications converter 
that uses TCP/IP communication packages. The 
gateway is responsible for the transparent conversion 
under TCP or UDP connections. The operation is 
determined by the parameterisation carried out in the 
internal configuration web menu. 
2.- COMMUNICATION
The device is equipped with a self-detecting 
10BaseT / 100Base TX connection for the physical 
connection of the TCP1RS+ converter to an Ethernet 
network. For its configuration, the device has an 
internal web site from which the user can define the 
network protocol used to communicate with the 
management software or communications system 
master. 
2.1.- Ethernet addressing
As the unit is connected to the master 
communication system by means of an IP 
connection, the addressing parameters must be 
configured. The configuration modes include the 
assignment of a fixed IP or configuration of a DHCP 
name. 
2.1.1.- Ethernet address assignment
To configure the IP address configuration in any of 
the available formats, run the IPSetup.exe 
executable supplied with the unit. 
2.1.2.- Fixed IP assignment
Run IPSetup and select the TCP1RS+ converter. To 
assign the fixed IP address, enter the MAC address 
shown on the permanent side label attached to the 
device, the format of which is 00:26:45:XX:XX:XX. 
 
In the IP Address field, enter the IP address being 
configured; do the same with the Netmask and the 
Gateway if necessary. After entering the device 
configuration, press “Configure” to send the 
configuration to the unit. 
2.1.3.- DHCP IP assignment
To assign the DHCP name, activate this option by 
clicking on the DHCP checkbox. Once the 
configuration fields have been enabled, enter the 
MAC address that can be seen on the permanent 
side label attached to the device, the format of which 
is 00:26:45:XX:XX:XX. In the Address, field, enter a 
free temporary IP address, which is within the 
working range of your computer. 
2.2.- Configuration
Once the unit is connected to the Local Area 
Network (LAN) and the IP address is configured or in 
the DHCP mode, the remaining configuration can be 
established in the IPSetup software console. When 
the unit has been fully configured, the configuration 
can be sent by clicking on “Configure”. 
2.2.1.- Network protocol
The unit can be connected to the master 
communications system by means of three types of 
network protocols and to a configurable port (TCP, 
UDP or Modbus/TCP). 
2.2.2.- Configuration of the Serial port
The communication parameters of the serial bus are 
fully configurable in terms of baud rate (1.2 bps to 
115.2 kbps), data bits (7 or 8), parity (none, odd or 
even) and stop bits (1 or 2). The data will be 
configured by default to 8 by selecting the 
Modbus/TCP communications protocol. 
2.2.3.- Device information
When the unit is connected with IPSetup, the top 
part of the screen shows the firmware version and 
the machine address of the device (the same 
address as that shown on the permanent side label). 
2.2.4.- Save changes
Once any change has been made to the 
aforementioned sections, the information must be 
saved using the “Configure” option. If you wish to 
return to the default configuration, select “Load 
default”. 
2.3.- Configuration of network protocols
2.3.1.- TCP Protocol
In totocol stack, TCP is the intermediate 
layer between t(IP) and the 
n general, applications need reliable 
communications. The IP layer offers an unreliable 
datagram service (no confirmation), so the TCP adds 
the functions required to offer a secure, error-free and 
zero loss service for the communications between 
two systems. 
-
Protocol: TCP Mode
-
Port: Destination TCP Port number
2.3.2.- UDP Protocol
User Datagram Protocol (UDP) is a minimum 
message-oriented protocol that has 
been documented in t tIn tUDP provides a simple 
interface between tand the 
UDP does not offer guarantees for 
the delivery of its messages and the UDP origin does 
not withhold the states of UDP messages sent to the 
network. UDP only adds tunctionality 
to tand tof the 
header and useful load. Any type of guarantees for 
the transmission of information must be implemented 
in higher layers. 
-
Protocol: UDP Mode
-
Port: Destination UDP Port number
2.3.3.- Modbus/TCP Protocol
Modbus/TCP is a variation or extension of the 
Modbus® protocol, which enables it to be used on the 
TCP/IP transport layer. Therefore, Modbus/TCP can 
be used throughout the Local Area Network or the 
Internet. This was one of the objectives that 
motivated its development (the specification of the 
protocol was submitted to the IETF, Internet 
Engineering Task Force). 
-
Protocol: Modbus/TCP Mode
-
Port: Fixed port number 502
2.3.4.- Tx Delay Rx Time
The TCP1RS+ converter uses two communication 
parameters to control the Modbus frames on the 
RS485 bus. 
-
Tx Delay: additional delay of the RS serial bus
-
Rx Time: maximum bus waiting time
Document Outline
- As the unit is connected to the master communication system by means of an IP connection, the addressing parameters must be configured. The configuration modes include the assignment of a fixed IP or configuration of a DHCP name.
 - To configure the IP address configuration in any of the available formats, run the IPSetup.exe executable supplied with the unit.
 - Run IPSetup and select the TCP1RS+ converter. To assign the fixed IP address, enter the MAC address shown on the permanent side label attached to the device, the format of which is 00:26:45:XX:XX:XX.
 - In the IP Address field, enter the IP address being configured; do the same with the Netmask and the Gateway if necessary. After entering the device configuration, press “Configure” to send the configuration to the unit.
 - To assign the DHCP name, activate this option by clicking on the DHCP checkbox. Once the configuration fields have been enabled, enter the MAC address that can be seen on the permanent side label attached to the device, the format of which is 00:26:45:XX:XX:XX. In the Address, field, enter a free temporary IP address, which is within the working range of your computer.
 - Once the unit is connected to the Local Area Network (LAN) and the IP address is configured or in the DHCP mode, the remaining configuration can be established in the IPSetup software console. When the unit has been fully configured, the configuration can be sent by clicking on “Configure”.
 - The unit can be connected to the master communications system by means of three types of network protocols and to a configurable port (TCP, UDP or Modbus/TCP).
 - The communication parameters of the serial bus are fully configurable in terms of baud rate (1.2 bps to 115.2 kbps), data bits (7 or 8), parity (none, odd or even) and stop bits (1 or 2). The data will be configured by default to 8 by selecting the Modbus/TCP communications protocol.
 - When the unit is connected with IPSetup, the top part of the screen shows the firmware version and the machine address of the device (the same address as that shown on the permanent side label).
 - Once any change has been made to the aforementioned sections, the information must be saved using the “Configure” option. If you wish to return to the default configuration, select “Load default”.
 - In the TCP/IP protocol stack, TCP is the intermediate layer between the Internet protocol (IP) and the application. In general, applications need reliable communications. The IP layer offers an unreliable datagram service (no confirmation), so the TCP adds the functions required to offer a secure, error-free and zero loss service for the communications between two systems.
 - User Datagram Protocol (UDP) is a minimum transport level message-oriented protocol that has been documented in the RFC 768 of the IETF.
 - In the Internet protocol family, UDP provides a simple interface between the network layer and the application layer. UDP does not offer guarantees for the delivery of its messages and the UDP origin does not withhold the states of UDP messages sent to the network. UDP only adds the multiplexing functionality to the application and the verification sum of the header and useful load. Any type of guarantees for the transmission of information must be implemented in higher layers.
 - Modbus/TCP is a variation or extension of the Modbus® protocol, which enables it to be used on the TCP/IP transport layer. Therefore, Modbus/TCP can be used throughout the Local Area Network or the Internet. This was one of the objectives that motivated its development (the specification of the protocol was submitted to the IETF, Internet Engineering Task Force).
 - The TCP1RS+ converter uses two communication parameters to control the Modbus frames on the RS485 bus.