4�4�4�- VARIABLES MODBUS

All

MODBUS map addresses are hexadecimal.

4�4�4�1�- Configuration variables

The

Read and Write functions are implemented for these variables.

Table 4:Modbus configuration variables CEM M-RS485.

Description

Address

Size

Valid data range

Default

value

Modbus address

0x03E8

16 bits

1 ... 254

1

Transmission speed

(Baudrate)

0x03E9

16 bits

0: 9600, 1:19200, 2: 38400

0: 9600

Communications configuration

0x03EA

16 bits

0: 8N1 ( 8 bits - No parity -1 stop bit)

1: 8E1 ( 8 bits - Even parity -1 stop bit)

2: 8O1 ( 8 bits - Odd parity -1 stop bit)

3: 8N2 ( 8 bits - No parity -2 stop bit)

4: 8E2 ( 8 bits - Even parity -2 stop bit)

5: 8O2 ( 8 bits - Odd parity -2 stop bit)

0

Impulse output type

0x0080

16 bits

0: Active energy, 1: Reactive energy

0

Impulse output weight

0x0081

16 bits

Wh/impulse 0 ... 99999

-

Cost per kWh

0x00B0

32 bits

0.0000 ... 9999.9999 with 4 decimal places

of resolution

-

KgCO

2

0x00B2

32 bits

0.0000 ... 9.0000 with 4 decimal places of

resolution

-

Note: Some MODBUS variables may not be available depending on the CEM energy meter

coupled to the

CEM M-RS485. See “4.4.4.7.- Available addresses by unit”

4�4�4�2�- Energy

The

Read function is implemented for these variables.

Table 5: Modbus variables: Energy

Description

Address

Size

Units

Total values

Imported active energy

0x0000

32 bits

Wh

Exported active energy

0x0002

32 bits

Wh

Q1 reactive energy

0x0004

32 bits

varh

Q2 reactive energy

0x0006

32 bits

varh

Q3 reactive energy

0x0008

32 bits

varh

Q4 reactive energy

0x000A

32 bits

varh

Partial values

Partial imported active energy

0x0030

32 bits

Wh

Partial exported active energy

0x0032

32 bits

Wh

Q1 partial reactive energy

0x0034

32 bits

varh

Q2 partial reactive energy

0x0036

32 bits

varh

Q3 partial reactive energy

0x0038

32 bits

varh

Q4 partial reactive energy

0x003A

32 bits

varh

Note: Some MODBUS variables may not be available depending on the CEM energy meter

coupled to the

CEM M-RS485. See “4.4.4.7.- Available addresses by unit”

14

CEM M-RS485

Instruction Manual